background image

N200-302-00

I56-4206-002  

on, the RF gateway will connect and program them with network 

information as necessary. The RF sensor then synchronises with 

its other associated devices as the RF mesh network is created by 

the gateway. (For further information, see the 

Radio Programming 

and Commissioning Manual

 - ref. N200-306-00.)

LED INDICATORS AND FAULT DESCRIPTION

The radio sensor has two LED indicators that show the status of 

the device.

4c

NOTE POLARITY

4a

Figure 4: Battery Installation 

and Rotary Address Switches

4 x Duracell 

Ultra 123

4d

4b

TESTING
Magnet Test

A correctly positioned test magnet will generate an alarm. Position 

the magnet (M02-04-00) as shown in Figure 5, after identifying the 

straight line ridge on the sensor base. To aid positioning, the sensor 

LEDs will turn on green for 1s when the alarm switch activates.

Direct Heat Testing (Hair dryer of 1000-1500 watts). 

Aim the heat toward the sensor from the side. Keep the heat source 

about 15 cm away to prevent damage to the cover during testing. 

The  sensor  should  signal  an  alarm  to  the  CIE  via  the  Gateway 

when the temperature at the sensor reaches 58°C.
Following testing, reset the alarm indication at the CIE (fire panel).

CLEANING

Use  a  vacuum  cleaner  and/or  clean,  compressed  air  to  remove 

dust and debris from the thermistor  and sensor cover as required 

(take care to avoid damaging the thermistor).

Note

When replacing batteries, all 4 will need to be replaced

LIMITATIONS OF HEAT SENSORS

These heat sensors will only work when connected to a compatible 

control panel. Heat detectors have operating limitations. They will 

not sense fires where heat does not reach the sensor, and may 

respond differently to varying heat conditions. Consideration must 

be given to the environment when selecting and siting fire sensors.
Heat sensors cannot last forever, and we recommend replacement 

after 10 years.

Figure 5: Test Magnet Position

+

+

+

+

1

2

3

4

LINE ON BASE

TEST MAGNET

EN54-25: 2008 / AC: 2010 / AC: 2012 Components Using Radio 

Links.  EN54-5: 2000 / A1: 2002 Class A1S and A1R Heat Detectors

for use in fire detection and fire alarm systems for buildings.

0333 16

NRX-TFIX58  DOP-IRF016

NRX-TDIFF  DOP-IRF017

Pittway Tecnologica S.r.l. 

Via Caboto 19/3, 34147 Trieste, Italy

ROTARY ADDRESS SWITCHES

+

Sensor  Status LEDs 

Sensor Status 

LED State 

Meaning 

Power-on initialisation  
(no fault) 

Long Green pulse 

Device is un-commissioned 
(factory default)  

3 Green blinks 

Device is commissioned 

Fault 

Blink Amber every 1s. 

Device has an internal trouble 

Un-commissioned  

Red/Green double-blink every 14s  
(or just Green when communicating). 

Device is powered and is waiting to be 

programmed. 

Sync 

Green/Amber double-blink every 14s 
(or just Green when communicating). 

Device is powered, programmed and 

trying to find/join the RF network. 

Normal

Controlled by panel; can be set to Red 

ON, periodic blink Red or OFF. 

RF communications are established; 

device is working properly. 

Idle (low power mode)  Amber/Green double-blink every 14s 

Commissioned RF network is in standby; 

used when the gateway is powered off. 

Magnet test 

1s green pulse when test magnet 

activates the internal switch. 

Device signals Alarm, all delays are 

removed for 10 minutes. 

Patents Pending

NOTE

Do not run more than 

one interface at a 

time to commission 

devices in an area.

Notifier by Honeywell, Brooks Road, Lewes, East Sussex, BN7 2BY, UK

EU Declaration of Conformity

Hereby, 

Notifier by Honeywell declares 

that the radio 

equipment types

 NRX-TFIX58 and NRX-TDIFF 

are in 

compliance

 with directive 2014/53/EU

The full text of the EU DoC can be requested from:

[email protected]

Содержание Notifier NRX-TDIFF

Страница 1: ...lled to the CIE via the Gateway when a head is removed from its base Figure 4 details the battery installation and the location of the rotary address switches Important Batteries should only be installed at the time of commissioning Warning Using these battery products for long periods at temperatures below 20 C can reduce the battery life considerably by up to 30 or more Observe the battery manuf...

Страница 2: ...eat conditions Consideration must be given to the environment when selecting and siting fire sensors Heat sensors cannot last forever and we recommend replacement after 10 years Figure 5 Test Magnet Position 1 2 3 4 LINE ON BASE TEST MAGNET EN54 25 2008 AC 2010 AC 2012 Components Using Radio Links EN54 5 2000 A1 2002 Class A1S and A1R Heat Detectors for use in fire detection and fire alarm systems...

Страница 3: ...avviso viene trasmesso al pannello di controllo tramite il gateway quando un sensore viene rimosso dalla base Nella figura 4 sono illustrati l alloggiamento delle batterie e i selettori rotanti Importante Installare le batterie esclusivamente al momento della messa in esercizio Attenzione L uso di prodotti a batteria a temperature inferiori a 20 C per periodi prolungati può ridurre considerevolmen...

Страница 4: ...atteristiche dell ambiente in cui verranno installati I rivelatori anti incendio non durano indefinitamente Se ne consiglia la sostituzione dopo 10 anni Figura 5 Posizione del magnete per il test 1 2 3 4 RIFERIMENTO SULLA BASE POSIZIONE DEL MAGNETE PER IL TEST EN54 25 2008 AC 2010 AC 2012 Componenti che utilizzano collegamenti radio EN54 5 2000 A1 2002 Rilevatori termici di classe A1S e A1R per l ...

Страница 5: ...alación de la batería y la ubicación de los selectores giratorios de dirección Configurar la dirección de lazo de antes de instalar las baterías ver sección siguiente Importante Instalar las pilas sólo en el momento de la puesta en funcionamiento Aviso Usar estos productos a pilas durante largos períodos a temperaturas inferiores a 20 C puede reducir considerablemente la duración de las pilas hast...

Страница 6: ...pre Recomendamos sustituirlos cada 10 años Figura 5 Posición del imán de prueba 1 2 3 4 LÍNEA EN LA BASE IMÁN DE PRUEBA EN54 25 2008 AC 2010 AC 2012 Componentes que utilizan conexiones vía radio EN54 5 2000 A1 2002 Class A1S and A1R Detectores de calor de clase A1S y A1R para el uso en sistemas de detección de incendios y alarmas de incendios para edificios 0333 16 NRX TFIX58 DOP IRF016 NRX TDIFF ...

Страница 7: ...randmeldeanlage Abbildung 4 zeigt die Batterieinstallation und die Position der Adressdrehschalter Wichtig Die Batterien erst zum Zeitpunkt der Inbetriebnahme einsetzen Warnung Bei längerem Einsatz bei Temperaturen von unter 20 C kann sich die Lebensdauer der Batterien beträchtlich verringern bis zu 30 und mehr Die Vorsichtsmaßnahmen des Herstellers hinsichtlich des Gebrauchs und die Anforderungen...

Страница 8: ...rmearten reagieren Bei der Auswahl und Anbringung von Rauchsensoren die Umgebungsbedingungen beachten Wärmesensoren halten nicht ewig Wir empfehlen einen Austausch nach 8 Jahren Abbildung 5 Position des Testmagneten 1 2 3 4 MARKIERUNG AM MELDERSOCKEL TESTMAGNET EN54 25 2008 AC 2010 AC 2012 Komponenten die Hochfrequenz Verbindungen nutzen EN54 5 2000 A1 2002 Klasse A1S und A1R Wärmedetektoren für d...

Страница 9: ...essage d alerte est signalé à la centrale via l interface lorsque la tête d un détecteur est retirée de son socle Se reporter à la Figure 4 pour plus de détails sur l installation des piles et roues codeuses sélection adresse Important Installer les piles uniquement au moment de la mise en service Avertissement L usage de ces produits fournit des piles dans les températures au dessus de 20 C pour ...

Страница 10: ... Les détecteurs thermiques ont aussi des limitations Tenir compte de l environnement pour sélectionner les détecteurs d incendie Les détecteurs thermiques ne sont pas conçus pour une utilisation indéterminée et nous conseillons de les remplacer au bout de 10 ans Figure 5 Position de l aimant de test 1 2 3 4 REPERE SOCLE AIMANT DE TEST ROUES CODEUSES SÉLECTION ADRESSE LEDs Etat Détecteur Etat du Dé...

Отзывы: