Honeywell NOTIFIER LDM Series Скачать руководство пользователя страница 43

LDM Series Instruction Manual —

 P/N 15885:H3 8/12/2019

43

AIM-200 Point Annunciation

System 5000 (UL 8th)

Figure B.11 illustrates the configuration of the LDM-R32 Relay Expander to activate alarms and troubles for up to 56 zones with the last 
eight relays dedicated to the CPU functions listed below.

TB1

1
2

3
4

5
6

7
8

4

3

2

1

5
6

7
8

1
2
3
4

5
6

7
8

1
2
3
4
5
6
7

8

TB3

TB4

TB5

TB2

TB6

TB1

1
2
3
4
5
6
7

8

1
2
3
4
5
6
7

8

TB2

Address #1

LDM-32

1st LDM-E32

2nd LDM-E32

3rd LDM-E32

System Status Indicators *

1   -   4

17   -   20
33   -   36
49   -   52

5   -   8

21   -   24
37   -   40
53   -   56

9    -   12

25   -   28
41   -   44

13  -   16

29   -   32
45   -   48

N.O. Contacts

N.O. Contacts

N.O. Contacts

N.O. 

Contacts

Trouble

Alarm

Alarm

Trouble

Trouble

Alarm

Alarm

Trouble

Common for TB1
Common for TB2

Common

for TB3

* System Functions

System Alarm
not used
not used
not used
System Trouble
Signals Silenced
not used
Supervisory

NAC Circuit #1 ON
NAC Circuit #2 ON
Municipal Tie ON
Alarm Relay ON
NAC Circuit #1 Trouble
NAC Circuit #2 Trouble
Municipal Tie Trouble
Alarm Relay Trouble

Common

for TB4

* It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56 circuits.

Figure B.11  Alarm and Trouble Relays with 8-Point Shift

Содержание NOTIFIER LDM Series

Страница 1: ...Lamp Driver Module LDM Series Instruction Manual Document 15885 Rev H3 8 12 2019 ECN 18 0305 ...

Страница 2: ...t provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predeter...

Страница 3: ...When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tighten ing may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal This system contains static sensitive com...

Страница 4: ...opriate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for print...

Страница 5: ... 9 Lamp LED Wiring 19 4 10 Control Switch Wiring 20 Section 5 Operating the Lamp Driver Module 21 5 1 LAMP TEST ACKNOWLEDGE 21 5 2 On Line LED 21 5 3 Graphic Annunciator Lamps LEDs 21 Section 6 LDM Communications 22 6 1 Receive Only LDM 32s 22 6 2 Receive Transmit LDM 32 22 Section 7 Electrical Ratings and Current Calculations 23 7 1 Lamp Driver Electrical Ratings 23 7 2 Supervision of LDM points ...

Страница 6: ...D 2 Lamp LED Driver Operation 50 D 3 Programming for Remote Annunciation 50 D 4 Installation Requirements 50 D 5 Configuration for the LDM 32 and AFP 100 51 Appendix E AFP 200 UL 8th 59 E 1 Capabilities 59 E 2 Trouble Indication 59 E 3 Lamp LED Driver Operation 59 E 4 Programming for Remote Annunciation 59 E 5 Installation Requirements 59 E 6 Configuration for the LDM 32 and AFP 200 60 Appendix F ...

Страница 7: ...tion directory https iq ulprospector com ACM 32A and AEM 32A ACM 16AT and AEM 16AT AFP 100 AFP 200 AFP 300 AFP 400 AM2020 AFP1010 Systems CPU 640 System 500 System 5000 AIM 200 NCA CPU 3030 SFP 1024 MPS 24A MPS 24B 1 3 Related Documentation Table 1 1 provides a list of document sources manuals containing additional information regarding the fire alarm control panels and components that the LDM Ser...

Страница 8: ... LDM Series Modules also interface to remote control switches which may be used to provide System reset System silence System acknowledge Temporary activation of NAC outputs Alarm relay activation Other control functions The LDM Series Modules interface to the host fire alarm control panel via an EIA 485 communications bus circuit A maximum of 32 LDM 32s may be connected to the power limited EIA 4...

Страница 9: ...arms and troubles and other functions Switch SW4 is used to configure the module to annunciate 32 alarms or 16 troubles A green ON LINE LED flickers to indicate ongoing communications with the host FACP One LDM 32 supports up to 3 LDM E32 modules The LDM 32 is supplied with 4 standoffs and screws for mounting to a chassis or custom backbox Output Connectors for Wiring to LEDs Security Key Switch T...

Страница 10: ...in fixed lengths of 24 and 48 inches J3 Ribbon Cable Connection From J2 This connector supports a single 26 conductor ribbon cable from J2 of the previous LDM 32 or LDM E32 Refer to Figure 3 3 J4 Keyswitch Input This two pin connector is provided as an input on LDM 32 and LDM E32 modules for an external security key switch Keyswitch contacts must be Normally Closed The keyswitch prevents unauthori...

Страница 11: ... drivers 2 6 Terminal Blocks TB1 Power Earth Ground and Supervision Removable terminal block TB1 appears only on the LDM 32 24 volts power limited regulated non resettable power from the host FACP or a compatible UL listed battery backed power supply must be connected to TB1 3 and TB1 5 Terminals TB1 2 and TB1 4 may be used to daisy chain the 24 volts to other LDMs or devices Earth ground must be ...

Страница 12: ... and or trouble signals from the LDM 32 and LDM E32 modules are used to activate the relays on the LDM R32 A maxi mum of two of these relay modules can be supported by an LDM 32 LDM E32 operating in alarm only mode providing a maximum of 64 alarm relays In alarm trouble mode one two or four LDM R32 modules may be connected to LDM 32 LDM E32s providing a maximum of 64 alarm and 64 trouble relays In...

Страница 13: ...chassis or enclosure as shown in Figure 3 2 One or three expanders can be installed when the LDM is configured for Alarm Trouble operation 4 Connect Expander Modules Optional Connect an Expander Ribbon Cable from the LDM 32 connector J2 to the LDM E32 connector J3 as illustrated in Figure 3 3 5 Connect EIA 485 annunciator wiring Pull all annunciator wiring into the enclosure Terminate the shield a...

Страница 14: ...irst LDM E32 expander module If multiple LDM E32 modules are to be used connect additional cables from J2 to J3 as shown in Figure 3 3 CHS4LST1 Figure 3 1 CHS 4L Mounting NOTE The LDM 32 can be mounted with one expander in the standard option board locations in panel specific chassis such as the CHS M2 and CHS M3 Select a location according to the instructions given for option boards in your FACP ...

Страница 15: ...TE The relay module can also be connected to an LDM E32 J10 J9 LAMP POW ER J11 J5 J6 J7 J8 J2 TB4 J5 J6 J7 J8 J10 K1 K2 K3 K4 K5 K6 K27 K28 K29 K30 K31 TB1 K32 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 LDM 32 LDM R32 LDM 32 or LDM E32 LDM R32 Chassis LDM 32 or LDM E32 LDM R32 Connect the Relay Power Ribbon Cable between J10 on the LDM R32 and J10 on the LDM 32 This connection supplies the power needed to en...

Страница 16: ... panel and LDMs is 6 000 feet 1 800 m The wiring must be an 18 AWG to 14 AWG 0 75 to 2 00 mm2 twisted shielded pair cable having a characteristic impedance of 120 ohms 20 Limit the total wire resistance to 100 ohms on the EIA 485 circuit and 10 ohms on the LDM power circuit Do not run cable adjacent to or in the same conduit as 120 volts AC service noisy electrical circuits that are powering mecha...

Страница 17: ...ouch earth ground at any junction points 4 6 EIA 485 Power and Relay Wiring EIA 485 TB2 Terminals 1 to 4 Do not T tap the EIA 485 circuit It will not function properly Wire as shown below Must be power limited See Section 4 3 EIA 485 Wiring Specifications for full details Leave a 120 ohm resistor installed across the EIA 485 Out terminals at the last LDM on the circuit see below All other LDMs sho...

Страница 18: ...must remain separated in the cabinet All power limited circuit wiring must remain at least 0 25 away from any nonpower limited circuit wiring Furthermore all power limited circuit wiring and nonpower limited circuit wiring must enter and exit the cabinet through different knockouts and or conduits A typical wiring diagram for the LDM R32 is shown T B2 T B2 EIA 485 EIA 485 4 3 2 1 T B2 4 5 6 7 3 2 ...

Страница 19: ...Figure 4 9 illustrates LEDs being powered by the 24V output from LDM 32 J9 pin 3 Power Limited Circuits Nonpower Limited Circuits LDM R32 Figure 4 7 Wiring Requirements NOTE All LEDs lamps being driven by the LDM series must be located in the same room as the modules Use cable kits for wiring from connectors on LDM J11 5 Common J6 J5 J4 SW ITCH MA TRIX LAMP PO W ER OUTPUTS J7 J8 J10 J9 Point Statu...

Страница 20: ...ions To determine the function of each switch and driver in a specific FACP application refer to the Appendices in this manual and the appropriate FACP Installation Manual J11 5 24 Common J6 J5 J4 SWITCH MA TRIX LAMP POWER OUTPUTS J7 J8 J10 J9 Note All LEDs must be in the same room as the LDM modules Point Status LEDs Use red for alarm points yellow for trouble points and green for output points U...

Страница 21: ... with the host control panel 5 3 Graphic Annunciator Lamps LEDs To adhere to standard fire alarm control panel convention and remain consistent with other products that may exist in the system the fol lowing color convention is employed Red Alarm LEDs To indicate an alarm condition for an Initiating Device Circuit software zone or addressable initiating device Yellow Trouble LEDs To indicate a tro...

Страница 22: ...t only If a Receive Transmit LDM is located at the end of the EIA 485 bus it will provide supervision of Receive Only LDMs located on the EIA 485 bus between the Receive Transmit LDM and the FACP See Figure 6 1 6 2 Receive Transmit LDM 32 LDMs that are configured to serve as full function annunciators can both receive status information for annunciation as well as transmit commands to the control ...

Страница 23: ...to the alarm calculation tables 5 Volt LED Power Limitations LED current desired mA Max of LEDs Number of Modules LDM 32 LDM E32 2 130 1 3 5 66 1 1 10 34 1 0 20 17 1 2 0 NOTE The LDM 32 drives 32 LEDs and each LDM E32 drives 32 more LEDs An LDM system configured for Alarm and Trouble Display Mode and employing three expanders could have as many as 128 LEDs all of which are activated during Lamp Te...

Страница 24: ...e System 500 Loss of communication results in System Trouble and Module Failure indications at the CPU A 3 Installation Requirements The EIA 485 circuit that communicates with the LDM must be connected to the CPU as illustrated in Figure A 1 The LDM 32 also requires filtered regulated power Refer to Figure A 2 for power supply connections A 4 MPS 24BPCC Main Power Supply System 500 Only Connect th...

Страница 25: ...piezo from sounding for any event 7 Switch Inhibit To disable the point I O control switches on the LDMs from functioning set this switch ON When inhibited the local Lamp Test switch continues to function In addition the Acknowledge Lamp Test switch will function only in a local capacity unrecognized by the host System 500 8 Flash Inhibit Set this switch ON to disable the flashing of LEDs associat...

Страница 26: ...Circuit s Controls Alarm Relay System 500 CPU Points LDM Alarm LED Red LDM Trouble Supv LED Yellow LDM Control Switchesa 1 Optional control switches are active only if all of these conditions are met a Receive Only DIP Switch 5 is set to OFF b Switch Inhibit DIP Switch 7 is set to OFF IZ 4 IZ 4A IZ 8 Alarm Status per Circuitb 2 If an IZ 4 IZ 4A or IZ 8 circuit is programmed on the System 500 as a ...

Страница 27: ... 4 illustrates the configuration of LDMs to annunciate alarms for up to 24 zones no zone troubles J6 J5 OUTPUTS J7 J8 J8 wire to LEDs view of LDM 32 Address 1 LDM 32 System Functions 1 8 9 16 17 24 System Status Indicators Notification Circuit 2 ON Green LED Notification Circuit 1 ON Green LED System Alarm Red LED Municipal Tie ON Red LED Alarm Relay ON Red LED not used Figure A 3 Alarm Points Onl...

Страница 28: ... Address 1 LDM 32 1st LDM E32 System Status Indicators 9 12 13 16 1 4 17 20 21 24 5 8 view of LDM 32 System Status Indicators NAC Ckt 1 ON Green LED NAC Ckt 2 ON Green LED Municipal Tie ON Red LED Alarm Relay ON Red LED NAC Ckt 1 Trbl Yellow LED NAC Ckt 2 Trbl Yellow LED Municipal Tie Trbl Yellow LED Alarm Relay Trbl Yellow LED Supervisory Yellow LED not used Signals Silenced Yellow LED System Tro...

Страница 29: ... 6 7 8 1 2 3 4 5 6 7 8 T B3 T B4 T B5 T B2 T B6 Address 1 LDM 32 System Functions 1 8 9 16 17 24 System Alarm not used not used not used NAC Circuit 1 ON NAC Circuit 2 ON Municipal Tie ON Alarm Relay ON N O Contacts N O Contacts N O Contacts N O Contacts Common for TB3 Common for TB1 Common for TB2 Common for TB4 Figure A 7 Alarm Relays with LDM R32 T B1 1 2 3 4 5 6 7 8 4 3 2 1 5 6 7 8 1 2 3 4 5 6...

Страница 30: ...N O Contacts N O Contacts N O Contacts Trouble Alarm Alarm Trouble Trouble Alarm Alarm Trouble Common for TB1 Common for TB2 Common for TB3 System Alarm not used not used not used System Trouble Signal Silenced not used Supervisory NAC Circuit 1 ON NAC Circuit 2 ON Municipal Tie ON Alarm Relay ON NAC Circuit 1 Trouble NAC Circuit 2 Trouble Municipal Tie Trouble Alarm Relay Trouble System Functions...

Страница 31: ...not latch they track or follow the status of each zone point that they are assigned to annunciate Table B 1 defines the ON status of each Lamp Driver output Software Required For the LDM to function properly the CPU must be operating under ROM1 5000 Part Number 73085 or higher Programming for Remote Annunciation After complete installation the LDM must be programmed into the System 5000 before it ...

Страница 32: ...MPS 24B TB2 Terminals 1 and 2 No more than 200 mA current can be drawn from these terminals in standby or alarm P4 P3 TB1 TB2 F1 CB1 P5 R27 P2 EARTHGND ACNEUTRAL ACHOT 24R COMMON 24 COMMON PO WERLIMITED BA T BA T MPS 24A Common TB3 2 24 VDC Power TB3 1 Figure B 2 Connecting Power from the MPS 24A CAUTION POWER LIMITED WIRING THE 24 VDC PROVIDED ON TB2 TERMINAL 3 IS POWER LIMITED ONLY WHEN USED WIT...

Страница 33: ...ive Only 6 Piezo Disable Set this switch ON to disable the piezo from sounding for any event 7 Switch Inhibit To disable the point I O control switches on the LDMs from functioning set this switch ON When inhibited the local Lamp Test switch continues to function In addition the Acknowledge Lamp Test switch will function only in a local capacity unrecognized by the host System 5000 8 Flash Inhibit...

Страница 34: ... Annunciator Address 1 8 CPU points CPU point shift not an option 8 unusable points redundant AIM 200 points 48 points mapped to the next six modules installed in the System 5000 which can also be AIM 200s for annunciation of their 8 software zones System 5000 CPU Points LDM Alarm LED Red LDM Trouble Supv Led Yellow LDM Control Switches Annunciator Point 1 Indicates System Alarm Indicates System T...

Страница 35: ...s ACK RES NAC 1 NAC 2 MUN TIE RELAY 8 CPU points 8 unusable AIM 200 points 48 points mapped to the next six modules installed NOTE AIM 200 detector and module addresses 97 98 and 99 may be used but cannot be point annunciated LDM Switch Position LDM 32 1st LDM E32 2nd LDM E32 3rd LDM E32 1 ACK Circuit 9 Circuit 25 Circuit 41 2 SIG SIL Circuit 10 Circuit 26 Circuit 42 3 RESET Circuit 11 Circuit 27 ...

Страница 36: ...d LDM E32 1 Circuit 1 Circuit 17 Circuit 33 Circuit 49 2 Circuit 2 Circuit 18 Circuit 34 Circuit 50 3 Circuit 3 Circuit 19 Circuit 35 Circuit 51 4 Circuit 4 Circuit 20 Circuit 36 Circuit 52 5 Circuit 5 Circuit 21 Circuit 37 Circuit 53 6 Circuit 6 Circuit 22 Circuit 38 Circuit 54 7 Circuit 7 Circuit 23 Circuit 39 Circuit 55 8 Circuit 8 Circuit 24 Circuit 40 Circuit 56 9 Circuit 9 Circuit 25 Circuit...

Страница 37: ...3 80 105 112 17 24 49 56 81 88 113 120 65 72 97 104 57 64 89 96 wire to LEDs view of LDM 32 System Status Indicators not Notification Circuit 1 ON Green LED System Alarm Red LED Notification Circuit 2 ON Green LED Municipal Tie ON Red LED Alarm Relay ON Red LED It is assuming this module expander annunciates points circuits 65 128 and is not functioning as a Receive Only annunciator Figure B 4 Ala...

Страница 38: ...3rd LDM E32 System Status Indicators 9 12 25 28 41 44 13 16 29 32 45 48 1 4 17 20 33 36 49 52 5 8 21 24 37 40 53 56 57 60 73 76 89 92 105 108 65 68 81 84 97 100 113 116 69 72 85 88 101 104 117 120 61 64 77 80 93 96 109 112 view of LDM 32 System Status Indicators NAC Ckt 1 ON Green LED NAC Ckt 2 ON Green LED Municipal Tie ON Red LED Alarm Relay ON Red LED NAC Ckt 1 Trbl Yellow LED NAC Ckt 2 Trbl Ye...

Страница 39: ...M E32 1 4 17 20 33 36 49 52 9 12 25 28 41 44 13 16 29 32 45 48 5 8 21 24 37 40 53 56 System Status Indicators view of LDM 32 System Status Indicators NAC Ckt 1 ON Green LED NAC Ckt 2 ON Green LED Municipal Tie ON Red LED Alarm Relay ON Red LED NAC Ckt 1 Trbl Yellow LED NAC Ckt 2 Trbl Yellow LED Municipal Tie Trbl Yellow LED Alarm Relay Trbl Yellow LED Supervisory Yellow LED not used Signals Silenc...

Страница 40: ... 5 6 7 8 T B 1 1 2 3 4 5 6 7 8 4 3 2 1 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 T B 5 T B 2 T B 1 1 2 3 4 5 6 7 8 1 8 33 40 25 32 41 48 49 56 9 16 17 24 System Functions 73 80 97 104 65 72 89 96 57 64 105 112 113 120 81 88 Address 2 LDM 32 LDM E32 System Alarm not used not used not used NAC Circuit 1 ON NAC Circuit 2 ON Municipal Tie ON Alarm Relay ON N O Contacts N O Contacts N O Contacts N O Cont...

Страница 41: ...2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 T B3 T B4 T B5 T B2 T B6 T B4 1 2 3 4 5 6 7 8 Address 1 LDM 32 LDM E32 1 8 33 40 25 32 41 48 9 16 17 24 System Alarm not used not used not used NAC Circuit 1 ON NAC Circuit 2 ON Municipal Tie ON Alarm Relay ON 49 56 System Functions System Functions N O Contacts N O Contacts N O Contacts N O Contacts Common for TB3 Common for TB1 Common for TB2 Common for TB4 It is as...

Страница 42: ...LDM E32 2nd LDM E32 3rd LDM E32 System Status Indicators 1 4 17 20 33 36 49 52 5 8 21 24 37 40 53 56 65 68 81 84 97 100 113 116 61 64 77 80 93 96 109 112 57 60 73 75 89 92 105 108 69 72 85 88 101 104 117 120 9 12 25 28 41 44 13 16 29 32 45 48 N O Contacts N O Contacts N O Contacts N O Contacts Trouble Alarm Alarm Trouble Trouble Alarm Alarm Trouble Common for TB1 Common for TB2 Common for TB3 Syst...

Страница 43: ...tem Status Indicators 1 4 17 20 33 36 49 52 5 8 21 24 37 40 53 56 9 12 25 28 41 44 13 16 29 32 45 48 N O Contacts N O Contacts N O Contacts N O Contacts Trouble Alarm Alarm Trouble Trouble Alarm Alarm Trouble Common for TB1 Common for TB2 Common for TB3 System Functions System Alarm not used not used not used System Trouble Signals Silenced not used Supervisory NAC Circuit 1 ON NAC Circuit 2 ON Mu...

Страница 44: ...oard ROM Part Number Central Processing Unit CPU 2020 73123 Display Interface Assembly DIA 1 73132 Loop Interface Board LIB 200 73117 for each LIB 200 C 4 NFS2 3030 NCA 2 and NFS 3030 EIA 485 Connections One EIA 485 circuit may be connected to the CPU 3030 CPU2 3030 or NCA 2 as shown in the accompanying illustration The NFS 3030 NFS2 3030 NCA 2 must be at the end of the EIA 485 circuit EIA 485 con...

Страница 45: ...below provided that the SIB 2048A is located in the center of the span illustrated below A 120 ohm terminating resistor is required at each end of the twisted pair R98 ACS Bus Termination Resistor Termination resistor built into board for NCA installations at physical end of ACS Bus If an NCA is not installed at end of Bus remove resistor R98 Remove all AC and DC power before cutting TB3 EIA 485 A...

Страница 46: ...n LDM operation and FACP programming under various specific applications refer to the appropriate FACP net work annunciator documents referenced in Section 1 3 Related Documentation on page 7 A xx P yy LDM Annunciator address is the range of 1 32 as set on the annunciator s rotary decimal switches LDM Annunciator point LDM Alarm Trouble Mode LDM Alarm Only Mode LDM 32 points 1 16 LDM 32 points 1 3...

Страница 47: ...N to disable the piezo from sounding for any event 7 Switch Inhibit Set this switch OFF to enable any control switches wired to the Lamp Driver If set ON switches wired to the Lamp Driver will not execute their intended functions but will serve only as a local Lamp Test for their respective points 8 Flash Inhibit Set this switch ON to disable the flashing of LEDs associated with unacknowledged eve...

Страница 48: ... 8 5 8 Points Alarm Trouble 9 12 9 12 Points Alarm Trouble 13 16 13 16 J6 J5 OUTPUTS J7 J8 Points Alarm Trouble 17 20 17 20 Points Alarm Trouble 21 24 21 24 Points Alarm Trouble 25 28 25 28 Points Alarm Trouble First LDM E32 Expander J6 J5 OUTPUTS J7 J8 Points Alarm Trouble 33 36 33 36 Points Alarm Trouble 37 40 37 40 Points Alarm Trouble 41 44 41 44 Points Alarm Trouble 45 48 45 48 Second LDM E32...

Страница 49: ...5 6 7 8 4 3 2 1 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 T B3 T B4 T B5 T B2 T B6 ADT LDM 32 LDM E32 1 8 33 40 1 8 33 40 1 8 33 40 1 8 33 40 N O Contacts N O Contacts N O Contacts N O Contacts Common for TB1 Common for TB2 Common for TB3 Common for TB4 Figure C 4 Alarm Only Relay Operation T B1 1 2 3 4 5 6 7 8 4 3 2 1 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 T B3 T B4 T B5 T B2 T B6 LDM 32 1st LDM E...

Страница 50: ...ED Driver Operation Lamp Driver outputs do not latch they track or follow the status of each zone point they are assigned to annunciate Table D 1 defines the ON status of each lamp driver output D 3 Programming for Remote Annunciation After complete installation the LDM must be programmed into the AFP 100 before it will function Program the LDM as if it were an annunciator Refer to the AFP 100 Tec...

Страница 51: ...igured as Receive Only 6 Piezo Disable Set this switch ON to disable the piezo from sounding for any event 7 Switch Inhibit To disable the point I O control switches on the LDMs from functioning set this switch ON When inhibited the local Lamp Test switch continues to function In addition the Acknowledge Lamp Test switch will function only in a local capacity unrecognized by the host AFP 100 8 Fla...

Страница 52: ...d not used not used 9 not used not used not used not used 10 not used not used not used not used 11 not used not used not used not used 12 not used not used not used not used 13 not used not used not used not used 14 not used not used not used not used 15 not used not used not used not used 16 not used not used not used not used LDM Switch Position LDM 32 1st LDM E32 2nd LDM E32 3rd LDM E32 1 not ...

Страница 53: ... to the AFP 100 system function LEDs listed below It is assumed that the 8 Point Shift will be selected only on systems containing less than 56 software zones or a total of 64 annunciator points or less J6 J5 OUTPUTS J7 J8 J5 Address 1 LDM 32 LDM E32 System Functions 25 32 1 8 33 40 9 16 41 48 17 24 49 56 wire to LEDs System Status Indicators System Alarm not used View of LDM 32 Figure D 1 Display...

Страница 54: ... Status Indicators 13 16 29 32 45 48 1 4 17 20 33 36 49 52 5 8 21 24 37 40 53 56 9 12 25 28 41 44 view of LDM 32 System Status Indicators not used not used not used not used Supervisory Yellow LED not used not used AC Fail Yellow LED not used not used Signals Silenced Yellow LED System Trouble Yellow LED System Alarm Red LED not Figure D 3 Alarm Trouble Annunciation of 56 Software Zones Without 8 ...

Страница 55: ... 44 45 to 48 49 to 52 53 to 56 LDM Module Address 02 LDM Output Connectors J5 J6 J7 J8 LDM 32 57 to 60 61 to 64 65 to 68 69 to 72 1st LDM E32 73 to 76 77 to 80 81 to 84 85 to 88 2nd LDM E32 89 to 92 93 to 96 97 to 99 Not used Table D 2 Alarm Trouble Setup Detectors without 8 Point Shift LDM Module Address 03 LDM Output Connectors J5 J6 J7 J8 ADT LDM 32 1 to 4 5 to 8 9 to 12 13 to 16 1st LDM E32 17...

Страница 56: ...o 20 21 to 24 25 to 28 29 to 32 2nd LDM E32 33 to 36 37 to 40 41 to 44 45 to 48 3rd LDM E32 49 to 52 53 to 56 57 to 60 61 to 64 LDM Module Address 04 LDM Output Connectors J5 J6 J7 J8 LDM 32 65 to 68 69 to 72 73 to 76 77 to 80 1st LDM E32 81 to 84 85 to 88 89 to 92 93 to 96 2nd LDM E32 97 to 99 Not used Not used Not used Table D 5 Alarm Trouble Setup Modules with 8 Point Shift LDM Module Address 0...

Страница 57: ...ctions LDM Module Address 02 LDM Output Connectors J5 J6 J7 J8 LDM 32 57 to 64 65 to 72 73 to 80 81 to 88 LDM E32 89 to 96 97 to 99 Not used Not used Table D 8 Alarm Only Setup Detectors with 8 Point Shift LDM Module Address 03 LDM Output Connectors J5 J6 J7 J8 LDM 32 1 to 8 9 to 16 17 to 24 25 to 32 LDM E32 33 to 40 41 to 48 49 to 56 57 to 64 LDM Module Address 04 LDM Output Connectors J5 J6 J7 J...

Страница 58: ...LDM E32 Address 04 Modules LDM 32 LDM E32 LDM E32 Address 03 Modules LDM E32 LDM 32 LDM E32 LDM E32 Address 02 Detectors LDM 32 LDM E32 LDM E32 Address 01 Detectors LDM E32 Note The LDM 32 addressed as 01 must be placed at the end of the EIA 485 wiring in order to provide electrical supervision of the wiring between all LDMs on the loop Figure D 5 Configuration for 198 Point Alarm Trouble Annuncia...

Страница 59: ...sage on the panel s 80 character LCD display E 3 Lamp LED Driver Operation Lamp Driver outputs do not latch they track or follow the status of those point they are programmed to annunciate Table E 1 outlines the annunciation of the various zones and functions E 4 Programming for Remote Annunciation After complete installation the LDM must be programmed into the AFP 200 before it will function Prog...

Страница 60: ...nowledge Lamp Test switch will function only in a local capacity unrecognized by the host AFP 200 8 Flash Inhibit Set this switch ON to disable the flashing of LEDs associated with unacknowledged events Flash Inhibit also disables the piezo from sounding Flash inhibit must be ON when using the relay expander module LDM R32 Alarm and Trouble Mode Without 8 Point Shift A second LDM 32 set to address...

Страница 61: ...ed not used not used not used 5 not used not used not used not used 6 not used not used not used not used 7 not used not used not used not used 8 not used not used not used not used 9 not used not used not used ACK 10 not used not used not used SIG SIL 11 not used not used not used RESET 12 not used not used not used DRILL 13 not used not used not used not used 14 not used not used not used not us...

Страница 62: ...annunciator points or less Figure E 2 Active Status of Software Zones with 8 Point Shift J6 J5 OUTPUTS J7 J8 Alarm Alarm Alarm Alarm T rouble T rouble T rouble T rouble J6 J5 OUTPUTS Address 1 LDM 32 1st LDM E32 2nd LDM E32 3rd LDM E32 System Status Indicators 13 16 29 32 45 48 1 4 17 20 33 36 49 52 9 12 25 28 41 44 5 8 21 24 37 40 53 56 Address 2 LDM 32 1st LDM E32 2nd LDM E32 57 60 73 76 89 92 6...

Страница 63: ...ms containing less than 56 circuits J6 J5 OUTPUTS J7 J8 Alarm Alarm Alarm Alarm T rouble T rouble T rouble T rouble J8 J7 OUTPUTS Address 1 LDM 32 1st LDM E32 2nd LDM E32 3rd LDM E32 System Status Indicators 13 16 29 32 45 48 1 4 17 20 33 36 49 52 9 12 25 28 41 44 5 8 21 24 37 40 53 56 System Status Indicators View of LDM 32 not used not used not used not used Supervisory Yellow LED Pre Alarm AC F...

Страница 64: ...ol Switches Acknowledge Signal Silence System Reset Drill F 2 Annunciator Programming LDM points must be programmed from the FACP before the LDM will function The AFP 300 400 NFS 640 NFS2 640 and NFS 320 employ the following format for annunciator points For programming the Lamp Driver Series into the FACP s memory for mapping system points and software zones to annunciator points and for details ...

Страница 65: ...ed Documentation on page 7 F 5 NFS 640 Connections The EIA 485 connections are made to TB13 on the CPU 640 as shown 24 VDC power limited non resettable power for the LDM is available from TB7 on the CPU 640 Do not use the two pins on TB7 marked resettable For more information on annunciator operation and FACP programming under various specific applications refer to the NFS 640 docu ments reference...

Страница 66: ...dule is required on the SFP 1024 to allow connection of annunciators to the panel A maximum of 32 devices can be connected to the EIA 485 output of the LED 10IM Module For more information on annunciator operation and FACP programming under various specific applications refer to the SFP 1024 doc uments referenced in Section 1 3 Related Documentation on page 7 24VNON RESETT ABLE 24V RESETT ABLE REL...

Страница 67: ...PLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the onl...

Страница 68: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...

Отзывы: