6.5.4 Transmitter Device Status Registers
The following are the values for the Device Status holding registers. These registers are
bit field registers represented as a 32-bit floating point values for Transmitters.
Value Transmitter Device Status
1
Transmitter Online
2
Low Battery Condition
►
4 Alarm Condition (WN571 only)
8
Sensor Error Condition
16
Sensor Overrange Condition
32
System Error Condition
64
Switch Input 1 Closed
128
Switch Input 2 Closed
►
256
Sq. Root Funct. (Diff. Pressure only - see
below)
Again, like Section 6.4.3, the status can be resolved by subtracting the largest number
listed above from the value received from the holding register, and then subtracting the
next highest and so on until the result is 0. Each of the values used indicate the
respective condition listed above.
For example, the holding register reads 9, then subtract 8 and get 1. Then subtract 1
from 1 and get 0. Thus from the list above, we have a Sensor Error Condition and the
Transmitter is online.
6.6 Square Root Function
The Square Root Function only works with the Differential Pressure Transmitter. When
the DP Transmitter is in Orifice mode, a Square Root calculation is performed. You have
the option to display the Square Root Calculation. If this option is enabled, it will be
displayed as Percent Square Root in WMT and sent to a Modbus Register.
The Square Root Calculation must be enabled through WMT. To display the Square Root
Calculation, first open the Configuration dialog box for the DP Transmitter and select the
Operation Mode tab. Make sure you have selected
Orifice Flow
from the mode menu.
Then, from the Flow Units drop-down list, select
Percent - Vol Flow
. If the Density check
box is selected, then
Percent - Mass Flow
can also be selected from the Flow Units
drop-down list to show the Square Root Calculation.
33
Содержание ISM BAND XYR 5000 LINE
Страница 1: ...Base Radio User Guide 900 MHz ISM Band FCC XYR 5000 Line 34 XY 25 05 Rev 4 08 06 ...
Страница 2: ...II ...
Страница 42: ...Figure 7 1 Overall Base Radio Dimensions 35 ...
Страница 44: ...Appendix B Base Radio Menu Map Figure A 1 Base Radio Menu Map 37 ...
Страница 49: ... 16986 Honeywell Industrial Measurement and Control 2500 W Union Hills Drive Phoenix AZ 85027 ...