total from the subtraction and subtract the next largest number possible and so on until
the result is zero. Each value that was used in the subtraction indicates that the
Transmitter is online.
For example: The On/Offline Status holding register contains the value 15. In this case
the largest value we can subtract is 8, which leaves a result of 7. Now we can subtract 4
from 7 and get 3. Now subtract 2 from 3 and we get 1. Finally we subtract 1 from 1 and
get 0, so we are done. Which Transmitters are online? We subtracted 8,4,2 and 1, and
these numbers correspond to Transmitters’ with RF IDs 1,2,3 and 4.
Note
An alternate method to determining which Transmitter(s) are online is to look at the
Base Radio Holding Register as a binary number with the rightmost bit representing
Transmitter 1 and the leftmost bit representing Transmitter 16. For example, the binary
representation for Transmitters 1-4 online is as follows:
0000000000001111
In another example, say the On/Offline Status holding register contains the value 6. We
can subtract 4 to get 2. Then we can subtract 2 to get 0. Thus Transmitter 2 and 3 are
online, but Transmitters 1 and 4 are offline.
6.5 Transmitter Holding Registers
The following are the Transmitter holding registers when used in the
Device ID Mapping
Mode
(First Table) and the
Register Mapping Mode
(Second Table).
6.5.1 Device ID Mapping Mode
Transmitter Holding
Registers
(DEVMODE Only)
Device ID
=
Base Radio Modbus ID + RF ID
Register Address
Description
Register Type
00001 Device
Type
00002 Device
Type
32-Bit IEEE
Floating Point
00003 Device
Status
00004 Device
Status
32-Bit IEEE
Floating Point
00005
Primary Sensor Value
00006
Primary Sensor Value
32-Bit IEEE
Floating Point
00007
Secondary Sensor Value
00008
Secondary Sensor Value
32-Bit IEEE
Floating Point
00009
Tertiary Sensor Value
00010
Tertiary Sensor Value
32-Bit IEEE
Floating Point
6.5.2 Register Mapping Mode
Transmitter Holding
Registers
(REGMODE Only)
Device ID
=
Base Radio Modbus ID
Register Address
Description
Register Type
00001 + (RF ID * 10)
Device Type
00002 + (RF ID * 10)
Device Type
32-Bit IEEE
Floating Point
00003 + (RF ID * 10)
Device Status
00004 + (RF ID * 10)
Device Status
32-Bit IEEE
Floating Point
31
Содержание ISM BAND XYR 5000 LINE
Страница 1: ...Base Radio User Guide 900 MHz ISM Band FCC XYR 5000 Line 34 XY 25 05 Rev 4 08 06 ...
Страница 2: ...II ...
Страница 42: ...Figure 7 1 Overall Base Radio Dimensions 35 ...
Страница 44: ...Appendix B Base Radio Menu Map Figure A 1 Base Radio Menu Map 37 ...
Страница 49: ... 16986 Honeywell Industrial Measurement and Control 2500 W Union Hills Drive Phoenix AZ 85027 ...