- 32 -
4.3 program specifications
Item Specifications
Step registration number
0~799step (maximum 800steps)
Step times
Maximum 99 hours and 59 minutes per step
Pattern registration number 0~29 (Maximum 30pattern)
Program link
Maximum 6 patterns
Link program registration
Maximum 10 links
Pattern REPEAT
1pattern all repeat X 1(Maximum repeat is 999 cycle)
Part repeat X 5(Maximum repeat is 999 cycle)
HOLD
Stops program operation, if HOLD key in the front panel is pressed
(Time counter stops and FIX control begins from that position)
Starts program operation, when HOLD key is pressed again.
(Time counter begins)
WAIT
1) Rear Wait
Time may exceed set time of the particular step. In this case,
remaining time is set as 0 and pending, if temperature
that was measured do not reach target value
±
WAIT set point.
It proceeds to the next step after it is confirmed that temperature reach
the range of set point
(target value
±
WAIT)
2) Front Wait
Proceeding of program is pending if temperature
that was measured do not reach the range of target
value
±
WAIT set point.
Setup range :
±
0 ~ 9.9
°
C
ADVANCE
If you press ADVANCE key in the display, the remaining time of the step is
set as 0 and moves to the next STEP.
Note) Operation of Advance while waiting
1) Proceeds to the next step in the case of Rear Wait
2) Time is set as 0 and set point (SP) is equal to target value in
the case of Front Wait.
PROGRAM RUN
1) Operates with RUN key in the display
2) Starts external signal : Input RUN/STOP,ON / 1 pulse
3) Starts time : It is possible to reserve time, day, and month
Note 1) Control output is ON with program RUN.
Note 2) Time begins is effective after operation of RUN in 1) or 2)
Program STOP
1) Operates with STOP key in the display
2) Input STOP for external signal : RUN/STOP ON / 1 pulse
(Note) If it is STOP, program stops and control output of the
total is OFF