- 7 -
2) Connection chart of digital input (SSR) terminal
Explanation for Reference
1. RUN output
— Terminal number: 8
— Content : Output is ON, when it is being operated.
In case operating mode is "STOP", "END", "READY",
"BREAK", or "TROUBLE" mode, output is OFF;
in case operating mode is "RUN", "HOLD", "WAIT", "COLD",
"HOT" mode, output is ON.
2. END output
— Terminal number : 9
— Content: Output is ON, if program control operation
is completed; otherwise, it is OFF.
Caution
The open collector output
of IPC500 is specified in
MAX 30 VDC, MAX 50mA,
internal resistance 47
Ω
.
When the load is relay,
please use a 24VDC relay.