- 19 -
Sequence of Operation
1. When you press any of keys, you will see a numeric keyboard in the screen below
and when you will insert any of PID and ARW constants in the input and press
the enter key, the setup will be all set, but if you press the ESC key the task will be
cancelled.
2. Early PID and ARW constants of every zone are setup as below:
P = 1.00 %, I = 1.20 Min, D = 0.30 Min, ARW = 100 %
3. constant setup boundary
P (Proportional band) : 0.0 ~ 99.99 %
I (Integral time) : 0 ~ 36.00 Min
D (Derivative time) : 0 ~ 36.00 Min
ARW : 0 ~ 100 %
3.5 INNER SIGNAL Setup Display Screen
This is a part which setups the INNER SIGNAL output items among DIGITAL outputs.
<Figure3.5.1>
EXIT
INNER SIGNAL1
TEMP
ITEM
(2) Object
select key
(3) Object value
select key
(5) Output operation selection key
Return to CONTROL SET screen
PV
SP
TYPE
DV
ABS
DEV
RANG
LOW
HIGH
LEVEL
ABS VALUE 0.0 -100 ~ 300
°
C
OPER DIFF 0.0 0 ~
±
9.9
°
C
DELAY(SEC) 0 0 ~ 99 SEC
PAGE
(1) Page conversion key
ABS
DEV
ABS
LOW
HIGH
OFF
ON
(4) Operating point selection key
TYPE
→
PV
TYPE
→
SP or DV
TYPE
→
PV
VALUE
SET RANGE
TYPE
→
SP or DV
(6) Absolute value,
Deviation value,
Minimum value
setup key
(7) Operation differential,
Maximum value
setup key
(8) ON/OFF DELAY time
setup key