- 8 -
3. DOWN output
— Terminal number : 11
— Content: While the pattern control is operated, output is ON if the
set temperature point decreases as in Figure 2.5.4. Output is
maintained as ON until WAIT is over and becomes OFF when
WAIT is over. If it is operated by a fixed command control , it is OFF.
4. TROUBLE output
— Terminal number : 12
— Content :
If any of the digital ALARM input (1~9) (terminal number 43,44,45,
46, 47, 48, 49, 50, 51) is ON, TROUBLE output is ON. To make
TROUBLE output OFF, you need to make ALARM input OFF and
press the “Clear” key in the troubleshooting display screen. At the time
when TROUBLE output occurs, all output except auxiliary (Present
value) output becomes OFF.
5. Output of 4 different types of Inner signals and Time signals
— Terminal Number:
INNER SIGNAL 1
→
terminal 13 TIME SIGNAL 1
→
terminal 17
INNER SIGNAL 2
→
terminal 14 TIME SIGNAL 2
→
terminal 18
INNER SIGNAL 3
→
terminal 15 TIME SIGNAL 3
→
terminal 19
INNER SIGNAL 4
→
terminal 16 TIME SIGNAL 4
→
terminal 20
— Content:
See reference explanation of Inner signal from pages 19 to 25
See reference explanation of Time signal from pages 28 to 30 in
“User Manual”
ON
ON
OFF
OFF
<
Figure 2.5.4
> DOWN SSR output ON-OFF