Detector Module Settings
In the following tables of the switch positions S1 have 2 positions.
on
off
The standard settings have a grey background.
Setting the response sensitivity
detector module
DM-TT-
50
DM-TT-
10
DM-TT-
01
S1
. 1
S1
. 2
0,8 %/m
0,12 %/m
on on
0,4 %/m
0,06 %/m
off on
1,0 %/m
0,2 %/m
0,03 %/m
on off
0,5 %/m
0,1 %/m
0,015%/m
off off
Setting the alarm delay
S1. 3
S1. 4
0 seconds
off
off
10 seconds
on
off
30 seconds
off
on
60 seconds
on
on
Setting the activating threshold
“air flow fault”
S1. 5
S1. 6
small on off
medium
off
on
large off off
very large
on
on
Setting the delay
“air flow fault”
S1. 7
S1. 8
0.5 minutes
off
on
2 minutes
on
off
15 minutes
on
on
60 minutes
off
off
Setting the fault signal
S1.
9
non-latched off
latched
on
Setting
LOGIC
⋅
SENS
S1.10
off
off
on
on