HI-SPEC unit_HON.doc
07/2011
6 of 12
Setting the alarm contacts
The contact type (break contact or make contact) of the alarm contacts is set using the jumper JU 1 to JU 6.
Alarm contact alert alarm
detector module I = Jumper JU2
Alarm contact alert alarm
detector module II = Jumper JU1
Alarm contact action alarm
detector module I= Jumper JU4
Alarm contact action alarm
detector module II = Jumper JU3
Alarm contact fire alarm
detector module I = Jumper JU6
Alarm contact fire alarm
detector module II = Jumper JU5
The following table shows the positioning of the jumpers:
X = pin pair bridge
O = pin pair open
The standard settings have a grey background.
Setting the alarm contacts
Jumper
Pin-No
.
JU1-6
1+2
JU1-6
2+3
break contact
O
X
make contact
X
O
A
B
Device Supports
A
B
Support Type MT-1
horizontal installation
Support Type MT-1
vertical installation