HI-SPEC unit_HON.doc 

07/2011   

1 of 12   

Installation Instructions 
Honeywell Air Sampling Smoke Detection System  
Honeywell HI-SPEC 

 
 

14

11

11

4

3

1

6

2

5

7

10

8

9

12

13

11

 
 

 

 

1 Operating-indicator 

light 

Indicator light for fault 

Indicator light for alert alarm-detector module I 

Indicator light for action alarm-detector module I 

Indicator light for fire alarm-detector module I 

Smoke level display 1 to 10 for detector module I 

Indicator light for alert alarm-detector module II  

Indicator light for action alarm-detector module II 

Indicator light for fire alarm-detector module II 

10 

Smoke level display 1 to 10 for detector module II 

11 

Pre-punched cable entries for connection to the central fire panel or power supply (input/output) 

12 

Connection pipe system I 

13 Connection 

pipe 

system II 

14 

Connection for air return 

Содержание HI-SPEC

Страница 1: ...ctor module I 5 Indicator light for fire alarm detector module I 6 Smoke level display 1 to 10 for detector module I 7 Indicator light for alert alarm detector module II 8 Indicator light for action alarm detector module II 9 Indicator light for fire alarm detector module II 10 Smoke level display 1 to 10 for detector module II 11 Pre punched cable entries for connection to the central fire panel ...

Страница 2: ...please follow the following instructions 3 Recover carefully the ventilator cover for the second air sampling duct self adhesive plastic cover 4 Break carefully the clasp for the connection of the second pipe system predetermined breaking point marked by II with a screwdriver from the housing Note The knockout is to be removed completely from the device 5 Make the required settings by setting the ...

Страница 3: ...06 m off on 1 0 m 0 2 m 0 03 m on off 0 5 m 0 1 m 0 015 m off off Setting the alarm delay S1 3 S1 4 0 seconds off off 10 seconds on off 30 seconds off on 60 seconds on on Setting the activating threshold air flow fault S1 5 S1 6 small on off medium off on large off off very large on on Setting the delay air flow fault S1 7 S1 8 0 5 minutes off on 2 minutes on off 15 minutes on on 60 minutes off of...

Страница 4: ... pair open The standard settings have a grey background Choose number of the detector modules Bridge Pin No BR1 1 2 1 detector module X 2 detector module O Setting the ventilator voltage Jumper BR3 on the base board and Jumper BR1 on the additional board allows the setup of the ventilator voltage The following table shows whether the jumpers are set or not X pin pair bridge O pin pair open The sta...

Страница 5: ...he contact type break contact or make contact of the collective fault is set using the jumper JU 7 and JU 8 collective fault contact detector module I Jumper JU8 collective fault contact detector module II Jumper JU7 The following table shows the positioning of the jumpers X pin pair bridge O pin pair open The standard settings have a grey background Setting the collective fault contact Jumper Pin...

Страница 6: ...dule I Jumper JU4 Alarm contact action alarm detector module II Jumper JU3 Alarm contact fire alarm detector module I Jumper JU6 Alarm contact fire alarm detector module II Jumper JU5 The following table shows the positioning of the jumpers X pin pair bridge O pin pair open The standard settings have a grey background Setting the alarm contacts Jumper Pin No JU1 6 1 2 JU1 6 2 3 break contact O X m...

Страница 7: ...g the device If necessary use the provided drilling jig Fix the device using four screws max of 6 mm for wall mounting and max of 4 mm for mounting by means of the device support MT 1 in order to guarantee a safe fixing and to limit vibra tions which occur 2 Fix the device by means of four screws in accordance with the mounting type to the wall or the device support Make sure the device is not fix...

Страница 8: ...X6 7 X4 7 8 X6 8 X2 7 8 JU6 RA3 I K6 X2 X5 1 X3 1 2 2 X1 1 2 JU7 RF II K7 3 3 4 4 3 4 JU1 RA1 II K1 5 5 6 6 5 6 JU3 RA2 II K3 7 7 8 8 7 8 JU5 RA3 II K5 X5 X1 X5 X3 X1 X5 X1 X5 X1 X5 X1 X5 X3 X1 X5 X1 X3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 detector module I Alert alarm relay L1 L1 L1 L1 L2 L2 L2 L2 L3 L3 L3 L3 L4 L4 L4 L4 L5 L5 L5 L5 L6 L6 L6 L6 L7 L7 L7 L7 L8 L8 L8 L8 fault contact det...

Страница 9: ...arm I just to connect if the contact as normally open programmed is standard X2 5 6 alarm resistance for alarm contact action alarm I just to connect if the contact as normally open programmed is standard X2 7 8 alarm resistance for alarm contact fire alarm I just to connect if the contact as normally open programmed is standard X3 1 X3 2 output line Fault II output line Fault II X3 3 X3 4 output ...

Страница 10: ...6 8 input line Fire alarm I input line Fire alarm I X8 1 X8 2 24 V reset input 0 V reset input X8 3 X8 4 24 V reset output 0 V reset output X9 1 X9 2 24 V input Alt Sens Alternate Sensitivity 0 V input Alt Sens Alternate Sensitivity X9 3 X9 4 24 V output Alt Sens Alternate Sensitivity 0 V output Alt Sens Alternate Sensitivity X10 1 X10 2 24 V supply voltage 0 V supply voltage X10 3 X10 4 24 V supp...

Страница 11: ...e 3 In order to initialize the connected pipe system press the Flow Init button S2 see figure of the corresponding detector module until the green operating indicator light of the device starts flashing The initialization is terminated after approx 5 seconds After a successful initialization the op erating indicator light is lit permanently 4 During and after initialization the pipe system must no...

Страница 12: ...been issued by notified product certification body ID no 0786 VdS The CE designation according to DIN EN 54 20 has been carried out 0786 WAGNER Group GmbH Schleswigstrasse 1 5 30853 Langenhagen 09 Nr 0786 CPD 20685 EN 54 20 2006 Air sampling smoke detector for fire detection and fire alarm systems in buildings 0 015 light obscuration m Class A B and C 0 1 light obscuration m Class A B and C 0 5 li...