Programming
Master Programming Level
PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds for all
devices programmed for PAS, press
1
while viewing Timer Screen #1. The following display will appear:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 005 for five
seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay
Screen which will indicate the new delay time.
Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of 001 to 180 seconds for all devices pro-
grammed for Pre-signal, press
2
while viewing Timer Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine
seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay
Screen which will indicate the new delay time.
Note that the FACP can have both PAS and Pre-signal timers programmed with values but a zone can only use either the PAS or Pre-sig-
nal feature, but not both.
Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-in delays
of the waterflow device. The factory default setting for Waterflow delay is 000 for no delay. To select a
Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow delay, press
3
while view-
ing Timer Screen #1. The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for twenty-
five seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the
Delay Screen which will indicate the new delay time.
AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the length of the
desired delay. Press
1
while viewing Timer Screen #2 to display the following:
A flashing cursor will appear in the lower left corner of the display. The factory default setting is 02 hours. Type the two digit AC loss
reporting delay in hours (00 to 24 hour delay). When the second digit is entered, the display will return to AC Loss Delay Screen #1.
TIMERS
1=PAS DELAY 120
2=PRE SIGNAL 120
3=WATERFLW DELAY 0
Timer Screen #1
PAS DELAY
RANGE 000-180 SECONDS
PAS Delay Screen
PRESIGNAL DELAY
RANGE 000-180 SECONDS
Pre-signal Delay Screen
TIMER
1=PAS DELAY 120
2=PRE SIGNAL 120
3=WATERFLW DELAY 0
Timer Screen #1
WATERFLOW DELAY
RANGE 00-90 SECONDS
Waterflow Delay Screen
TIMER
1=AC LOSS DELAY 2
Timer Screen #2
AC LOSS DELAY
RANGE 00-24 HOURS
AC Loss Delay Screen #1
NOTE:
Upon the loss of AC power at the control panel, relays programmed for AC Loss will transfer immediately, regardless of the
AC
Loss Delay
setting. If no troubles other than AC Loss exist in the panel, the System Trouble relay will delay activation for the duration of the
AC Loss Delay
setting.
60
GF505 & GF510 Manual —
P/N
53164
:B5 6/12/2018