Section 3: Programming
3.1 User Programming
The GF505/GF510 FACP is completely field programmable using the panel keypad and requires no special software skills.
Site-specific programming may be accomplished in the following ways:
•
Manual programming or editing, using the FACP keypad
•
Remote Programming and Editing Feature - allows creation and editing of site-specific custom programs using a Windows-based
computer and modem. For programs requiring a large amount of data entry, this method may be preferred. A PK-CD programming
CD ROM can be ordered for this purpose
•
Local Programming and Editing Feature - allows creation and editing of site-specific custom programs using a Windows-based
computer and USB connection. For programs requiring a large amount of data entry, this method may be preferred. A PK-CD
programming CD ROM can be ordered for this purpose
The
System All Normal
screen will be displayed in a programmed system with no active alarms, troubles or supervisories, as illustrated
below:
Read Status mode can be entered while the panel is in any mode of operation. If an alarm or supervisory event exists at the panel, the
event must be cleared before entering Programming mode. To access any of the programming or read status features, the
Enter
or
Mode
key must be pressed, which will cause the LCD to display the following:
Pressing
1
, while this screen is being displayed, will cause the control panel to enter the Read Status Mode which allows the user to view
the programmed features and status of the control panel The Read Status feature is not password protected. Refer to “Read Status” on
page 92 for a detailed description of this feature.
Pressing
2
will select user Programming Mode which may only be accomplished by an authorized person. After pressing
2
, a screen will
prompt for a password. After entering the correct password, the user may select from a list of programming options.
Pressing
4
will select Remote Download which allows the user to enable the remote programming option. Refer to “Remote Download”
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated
below:
Program feature or option
Permitted in UL
864? (Y/N)
Possible settings
Settings permitted in UL 864
Trouble Call Limit
N
Refer to “Trouble Call Limit (Dialer Runaway Prevention)” on
Trouble Call Limit = 0 (factory default): unlimited calling to
Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique trouble
to from 1 to 99 within a 24 hour period
Trouble Call Limit = 0
for
unlimited Central Station trouble
calls
Remote Download
Y
Refer to“Remote Download” on page 98.
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Remote Download
Proprietary
Yes
for Proprietary system
intended to protect only
contiguous properties
Combo
Y
Refer to Table 3.1 on page 48.
One Waterflow and one
Supervisory device
Combo w/AutoResettable
Superv
Y
Refer to Table 3.1 on page 48.
One Waterflow and one
Supervisory device
!
CAUTION: FIRE PROTECTION ENABLED
WHILE PROGRAMMING THE FACP, THE FIRE PROTECTION CAPABILITIES OF THE CONTROL PANEL ARE
ENABLED. PROGRAMMING MODE TIMES-OUT AFTER 10 MINUTES OF INACTIVITY.
SYSTEM ALL NORMAL
10:00A 060718
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FUTURE USE
4=REMOTE DOWNLOAD
GF505 & GF510 Manual —
P/N 53164:B5 6/12/2018
43