Master Programming Level
Programming
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and not a
false alarm. This feature is selected by pressing
3
while viewing the Edit Zone Screen #2 so that the display
reads
Verification On
. Each time the
3
key is pressed, the display will toggle between
Verification On
and
Verification Off
. For a detailed description, refer to “Alarm Verification (None or One Minute)” on page 91.
Note that verification can only be enabled for a zone that is programmed as a smoke detector type. Zones
programmed for any other type will not allow the Verification feature to be enabled.
Do not use the verification feature if a mix of smoke
detectors and normally open contact devices are connected to the same zone.
INPUT ZONE
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Input Zone Screen #2
GF505 & GF510 Manual —
P/N 53164:B5 6/12/2018
49