1
RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
Section 1: Overview
1.1 RPS-1000 Description
The RPS-1000 Intelligent Power Module provides additional power and circuits to the IFP-2100, IFP-2100ECS, IFP-2000, IFP-
2000ECS, IFP-1000, IFP-1000ECS, IFP-300, IFP-300ECS, IFP-100, IFP-100ECS or IFP-75 FACPs. The RPS-1000 can power all the
FACP compatible modules, including SLC devices (via a Model 5815XL or 6815 SLC Expander), remote annunciators, notification
appliances, auxiliary power modules, and all other compatible modules. RPS-1000 is available in a black cabinet as P/N RPS-1000B*
The RPS-1000 has six Flexputs™ and two programmable relays. Outputs are rated 3.0 A (6.0 A total for each RPS-1000). Relays are
Form C rated at 2.5 A @ 24 VDC. Outputs and relays are fully programmable.
The RPS-1000 is optically isolated, providing ground loop isolation and transient protection. It functions as an SBUS repeater which
conditions the RS-485 signal and allows the module to drive up to 6,000 feet of additional SBUS wiring.
The RPS-1000 is housed in a metal cabinet that is identical in size to the IFP-1000/IFP-1000ECS FACP cabinet. This cabinet is large
enough to house two 17 AH batteries. The RPS-1000 cabinet provides mounting studs for two Model 5815XL or 6815 SLC Expander
modules.
The RPS-1000 communicates to the main FACP via the SBUS. Each RPS-1000 provides an additional 6,000 feet of SBUS wiring length
to the main panel. As the drawings on the next pages illustrate, this allows you to distribute modules, SLC devices, and outputs through-
out an extremely large facility.
As well as expanding the wiring length capabilities of the FACP, the RPS-1000 also expands the power capabilities by an additional 6.0
A of current.
*
All references to RPS-1000 within this manual are applicable to the RPS-1000B.
1.1.1 Maximum Number of SBUS Modules
The chart below shows the maximum number of compatible modules that can be used in an Intelligent installation. Modules can be dis-
tributed among the main panel SBUS and each additional RPS-1000 SBUS in virtually any combination.
NOTE:
The IFP-100 and IFP-75 do not use 5815XL or 6815 SLC expanders.
Module or Device
Maximum Number
RPS-1000/RPS-1000B Intelligent Power
Module
8 per IFP-1000/ECS, IFP-100/ECS, IFP-50 or IFP-75 installation
16 per IFP-300/ECS installation
63 per IFP-2100/ECS or IFP-2000/ECS installation
RA-100 or RA-1000 Remote Annunciator
8 per IFP-50 or IFP-75 installation
12 per IFP-100/ECS, IFP-1000/ECS installation
16 per IFP-300/ECS installation
31 per IFP-2100/ECS installation
RA-2000 Remote Annunciator
63 per IFP-2100/ECS or IFP-2000/ECS installation
6815 SLC Expander
63 per IFP-300/ECS or IFP-2100/ECS installation
5815XL SLC Expander
7 per IFP-1000/ECS installation
63 per IFP-300/ECS, IFP-2000/ECS or IFP-2100/ECS installation
5824 Serial/Parallel Modules
4 per IFP-1000/ECS, IFP-300/ECS, IFP-2000/ECS or IFP-2100/ECS
installation
Outputs
6 per IFP-1000 or IFP-1000ECS / RPS-1000
Conventional Relays
2 per IFP-1000 or IFP-1000ECS / RPS-1000
Содержание Farenhyt RPS-1000
Страница 49: ......