RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
28
Flexputs™ I/O Circuits
Hardware Installation
3.5.4 Installing 2-Wire Smoke Detectors
Any compatible UL listed two-wire smoke detector can be used with the RPS-1000 panel (see “Compatible Devices” on page 1 for list
of compatible smoke detectors). Figure 3.12 and Figure 3.13 illustrate how to connect a UL listed 2-wire detector to the control panel.
Class B Installation
To install a Class B two-wire smoke detector, wire as shown in Figure 3.12.
Figure 3.12 Two-Wire Class B Smoke Detector
2-Wire Class A Smoke Detector Installation
To install a Class A two-wire smoke detector, wire as shown in Figure 3.13.
Figure 3.13 Two-Wire Class A Smoke Detector Connections
Model Number
FACP Installation Manual
IFP-2000ECS
151430-L8
IFP-1000ECS
151460
IFP-100ECS
151458
IFP-300ECS
LS10145-001SK-E
IFP-2100ECS
LS10143-001SK-E
Note:
I/O circuit 5
used as an example.
Any I/O circuit
could be used.
EOL
4.7 k
Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.
Содержание Farenhyt RPS-1000
Страница 49: ......