RPS-1000 / RPS-1000B Manual - P/N 151153:N 08/09/2017
26
Flexputs™ I/O Circuits
Hardware Installation
3.5.2 Releasing Operations
Approved releasing solenoids are list in Table 3.1
Do not mix cross alarming zones with smoke verification zones. There must be at
least two automatic detection devices in each protected space. Spacing must be reduced to 0.7 times the linear spacing in accordance
with NFPA 72.
Class B Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A.
To install a Class B notification appliance circuit:
1.
Wire Class B Notification appliances as shown in Figure 3.8.
2.
Configure the circuit through programming.
Figure 3.8 Class B Notification Appliance Circuit Wiring
Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual.
To install a Class A notification appliance circuit:
1.
Wire the Class A notification appliances as shown in Figure 3.9.
2.
Configure the circuit for Class A in programming (see the
FACP Installation manual
).
Figure 3.9 Class A Notification Appliance Circuit Configuration
Table 3.1 Approved Releasing Solenoids
Manufacturer
Part Number
Rating
Current
Freq
Asco
T8210A107
24 VDC
3A max
0 Hz
8210G207
24 VDC
3A max
0 Hz
Alarm
Polarity
EOL
4.7 k
Supervised
Power Limited
Notification Wiring
Regulated
Regulated
NOTE:
In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
Figure 3.9 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5