Troubleshooting
Excel 800
EN1B-0375GE51 R0910
78
Service LED of I/O Modules
case Service LED
Meaning
Remedy
1
LED remains OFF after
power-up
If the power LED is also OFF, then
– Defective
device
hardware
– Possible power supply problems, clock
problems, defective processor
►
Replace hardware.
2
LED is lit continuously after
first power-up
L
ON
W
ORKS
Bus I/O modules:
– Defective
hardware
Panel Bus I/O modules:
– I/O module has not yet been configured
by XCL8010
– Boot loader is active
– Failure during last firmware download
– Checksum
error
L
ON
W
ORKS
Bus I/O modules:
►
Replace hardware.
Panel Bus I/O modules:
►
Set the hex address to the position configured
with CARE
►
Ensure that I/O Bus switch S2 of XCL8010
Controller is set to position "Panel"
►
Check the Panel Bus wiring:
- Check for cable breaks
- Check for cable short-circuits
- If using separate transformers: Check ground
connection
►
Eliminate any mixture of Panel Bus I/Os and
LonWorks I/Os on same wire
►
Allow XCL8010 to configure I/O module
►
Unplug and replug the module
►
If problem persists, replace hardware
3
Alternating flash between
service LED and power LED
Download error or application checksum error.
Boot loader is running
►
Panel Bus I/O modules:
Wait until rebooting (firmware download) has
been completed
►
L
ON
W
ORKS
Bus I/O modules:
Using CARE or Excelon, reload the APBG file
into the I/O module.
4
LED flashes at power up,
goes OFF, and then is lit
continuously
L
ON
W
ORKS
Bus I/O modules, only:
L
ON
W
ORKS
Bus I/O module lacks application
►
Download application
5
LED repeatedly blinks
ON for 1 sec and
OFF for 1 sec
L
ON
W
ORKS
Bus I/O modules, only:
L
ON
W
ORKS
Bus I/O module is unconfigured, but
has an application
►
Set module to configured mode
6
LED remains OFF after a
short ON duration
I/O module is configured and running normally
No action necessary
7
LED flashes continuously in
following pattern:
4 x ON/OFF followed by
pause
Sensor failure of analog input module
(in case of L
ON
W
ORKS
Bus I/O modules, this
behavior can occur only if the appropriate NV
has been bound)
►
Check sensor or connection
►
Check sensor configuration
8
LED flashes continuously in
following pattern:
5 x ON/OFF followed by
pause
L
ON
W
ORKS
Bus I/O modules, only: L
ON
W
ORKS
I/O Bus module has received the wink
command from network, physical outputs are
unaffected
No action necessary
9
LED flashes continuously in
following pattern:
6 x ON/OFF followed by
pause
Boot loader problem or hardware defect
►
Replace hardware
10
LED flashes continuously in
following pattern:
7 x ON/OFF followed by
pause
Communications failure
►
Check bus wiring
►
Ensure that I/O Bus switch S2 of XCL8010
Controller is set to correct position
►
Ensure that L
ON
W
ORKS
Bus I/O modules and
Panel Bus I/O modules are not sharing same
bus
►
In case of Panel Bus I/O modules, only:
Check for incorrect HEX addresses (2 Panel Bus
I/O modules using same HEX address)
►
In case of L
ON
W
ORKS
Bus I/O modules, only:
Check heartbeat
Table 78 Service LED of I/O modules