Troubleshooting / Service
Self Diagnostics
Release M
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
207
April 2017
Device status
When required, the results of the power-up tests can be checked to determine the reason the recorder has
gone to “Failsafe”.
The following procedure in Table 9-3 tells you how to display the results of the latest tests run. Table 9-4
lists the tests, the reason for the failure, and how to correct the problem.
Table 9-3 Procedure for displaying the device status
Step
Operation
Press
Action/Result
1
Select STATUS
Set Up Group
SET
UP
Until you see:
Upper Display:
READ
Lower Display:
STATUS
2
Read the status tests
results
FUNC
Until you see:
Upper Display:
NO
or
YES
(YES indicates a failure)
Lower Display:
FAILSAFE
Successive presses of the
FUNC
key will display the
results of the tests (PASS or FAIL) in the following
order:
RAM TEST
CONFTEST
CAL TEST
FACT CRC
BATTERY
Identify the problem from the error message and
correct the failure as shown under "Lower Display
Indication” in Table 9-4.