Input
Calibration -
Calibration
Set Up and Wiring for PV Inputs
188
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
Release M
April 2017
Radiamatic, millivolts, and volts inputs (except 0
–10 Volts)
Refer to Figure 7-7 and wire the recorder according to the procedure given in Table 7-10.
Table 7-10 Set up wiring procedure for Radiamatic, Millivolts, and Volts inputs
(except 0-10 Volts)
Step
Action
1
Connect the copper wire to the calibration source (see Figure 7-7).
2
Connect the other end of the copper wire to the clamp type terminals in the plug for the
applicable input connector (J2).
3
Reinstall the plug into the input connector (J2) on the applicable circuit board for input 1 or
input 2.
#2 #1
22093
+
_
Copper wires
_
+
Calibration source
Plug J2
MA
W1
Be sure W1/MA
jumper is in position
W1 on the input board.
T/C
RTD
Be sure W3 jumper
is in position T/C
on the input board.
Figure 7-7 Calibration set up diagram for Radiamatic, Millivolts, and Volts inputs
(except 0-10 Volts)