Configuration Parameter Definitions
Auxiliary Output Set Up Group
110
DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual
Release M
April 2017
Lower Display
Prompt
Upper Display
Range of Setting or Selection
Parameter Definition
AUX OUT
(continued)
SP 1
SETPOINT 1
—Represents the value of the setpoint in
units of PV for Loop 1.
PV 2
PROCESS VARIABLE 2
—Represents the value of the
process variable for Loop 2.
DEV 2
DEVIATION 2 (PROCESS VARIABLE MINUS
SETPOINT)
—Represents –100 to +100% of the
selected PV span for Loop 2.
See Example at DEV 1.
OUT 2
OUTPUT 2
—Represents the displayed controller output
in percent (%) for Loop 2.
SP 2
SETPOINT 2
—Represents the value of the setpoint in
units of PV for Loop 2.
4 mA VAL
Low Scale Value
within the range of the selected
variable to represent 4 mA
AUXILIARY OUTPUT LOW SCALING FACTOR
—Use
a value in engineering units for all selections above
except Output.
Use value in percent (%) for Output. (Output can be
between
–5 and +105%.)
20mA VAL
High Scale Value
within the range of the selected
variable to represent 20 mA
AUXILIARY OUTPUT HIGH SCALING FACTOR
—Use
a value in engineering units for: Input 1, Input 2,
Process Variable, Deviation,* and Setpoint.
Use a value in percent (%) for Output. (Output can be
between
–5 and +105%.)
*When Deviation is selected, only one operating
parameter will be entered. This value represents the
deviation level that will produce 20 mA output. Zero
deviation will produce a center scale (12 mA) output. A
negative deviation equal in magnitude to the Auxiliary
Output High Value will produce a low end (4 mA) output.
Repeat for AUX OUT 2 and AUX OUT 3.