DC1010/1020/1030/1040 PRODUCT MANUAL
4
Main Control
Range: 0.0~200.0%
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
4.2
Level 2
Return to
‘P1’
Proportional Band
Main Control
Integral Time
Main Control
Derivative Time
Main Control
Dead-band Time
Main Control
Auto Tuning off-set
Main Control
Proportional Cycle
Main Control
Hysterisis
Sub Control
Proportional band
Sub Control
Integral Time
Sub Control
Derivative Time
Sub Control
Proportional Cycle
Sub Control
Hysterisis
Main Control
Gap (Output 1)
Sub Control
Gap (Output 2)
Function Lock
ON/OFF at P1=0
Range: 0~3600 sec
Integral off at I=0
Range: 0~900 sec
Derivative off at D=0
Don’t care.
Range: 0~USPL
Output (SSR
Æ
1, 4~20mA
Æ
0, relay
Æ
over 10)
Range: 0~150 sec * Refer to 8.10 Cycle Time
For ON/OFF control(P1=0) only(Range: 0~1000)
OFF : PV>(SP+HYS1)
Same as P1
Same as I1
Same as D1
Same as CYT1
Same as HYS1
For dual output use only, set the value turning
Turning Point = SP-GAP1 ; OFF
For dual output use only, set the value turning
Turning Point = SP+GAP2 ; ON
* Refer to 4.4.1(P.7)
ON : PV<=(SP-HYS1)
ON/OFF at P2=0
S
et d
u
al ou
tp
u
t, M
en
u
will b
e d
isp
la
ye
d
.
R
ef
er
to
8.1.2
LCK=0100, To enter Level 1 & 2 and to change their parameters allowed
.
LCK=0110, To enter Level 1 & 2 and to change the parameters on Level 1 allowed.
LCK=0001, To enter Level 1 only and to change SP allowed.
LCK=0101, Nothing allowed except to change LCK.
LCK=0000, To enter any Level(except SET Level) and to change their parameters