DC1010/1020/1030/1040 PRODUCT MANUAL
20
8.2
RAMP & SOAK
8.2.1
RAMP
i)
Set “SET2.1= 1”, “SET4.1= 1” at Set level
ii)
Set “ALD 3 = 9” at Input level
iii)
Then, “AL 3” menu will not be displayed
Range = 00.00~99.99 (°C/minute)
If RAMP not used, set ALD 3 = 0
8.2.2
SOAK
i)
ALD1/ALD2 = 19
ii)
Then, AL1/AL2 will be displayed
Range = 00.00~99.59 (hour/minute)
Example)
SP = 100
°
C, RAMP = 10.00
°
C/minute
Time(minute) = 10 minute
Æ
AL1 = 00.10
PV = 25
°
C
PV
SP
PV
SP
°
C
t
100
°
C
PV=25
°
C
Time on
If PV
≥
SV(100
°
C)
SOAK Menu