DC1010/1020/1030/1040 PRODUCT MANUAL
21
8.3
Remote SP(Second Input)
8.3.1
Hardware must be mounted
8.3.2
Set ‘INP2’ to 1 or 2 (ANL2, ANH2 used for Calibtration)
8.3.3
SET 0.3 = 1 means Remote SP from Input 2 channel
(*SET 0.3 = 0 means Local SP)
8.4
Alarm Timer ALT1/ALT2/ALT3 description
8.4.1
ALT 1 = 0 means ‘flicker alarm’ if AL 1 is ON
8.4.2
ALT 1 = 99.59 means ‘continuous alarm’ if AL 1 is ON
8.4.3
ALT 1 = 00.01~99.58 means AL 1 is on delay timer
(* Use for large EMI affect controller)
8.5
Function SET A(LEVEL3)
8.6
Function SET 8
8.6.1
SET 8.1 = 0
Non
SET 8.1 = 1
Program Repeat
8.6.2
SET 8.2 = 0
Non (program model only)
SET 8.2 = 1
Power failure access
8.6.3
SET 8.3 = 0
Zero start (program model only)
SET 8.3 = 1
PV start
8.6.4
SET 8.4 = 0
Non
SET 8.4 = 1
Display will be transferred to single display
(Don’t change it)
* ‘SET 8.4 = 1’ can make return to double display
PV
SP
If SET A.1 = 1 set, AL1 relay reversed
If SET A.2 = 1 set, AL2 relay reversed
If SET A.3 = 1 set, AL3 relay reversed
If SET A.4 = 0 set, program run alarm
If SET A.4 = 1 set, program end alarm
Program model only
DC1010 is not available.
‘a’ contact only