DC1010/1020/1030/1040 PRODUCT MANUAL
10
4.5.1
This program has 2 patterns, each pattern contains 8 segments.
The segment can be arranged a period of RAMP status or SOAK status.
4.5.2
Terminologies
Pattern
: A program consists of some segments
Step
: A RAMP a SOAK status
RAMP status
: The status with changing SP
SOAK status
: The status with fixed SP
4.5.3
Operating
1)
Key functions (No changing parameters)
(START)
: To start program procedure, PRO in panel flicker
(WAIT)
: To suspend program procedure, PRO in panel will
stop flicker but light
+SET (JUMP) : To jump segment
+SET (RESET) : To reset program procedure, PRO in panel will be
“off”
2)
Alarm function
If ALD1 to be set 07 (*refer to the selection),
AL1 to be set 2 (AL1=2, it means alarm in segment 2 end),
ALT1 to be set 00.10 (alarm time 10 sec.).
*In this case, when program proceeds to segment 2 end, ALM1 relay
will be on 10 sec.
3)
End function
If ALD to be set 17 (* refer to the selection), this program will be end
in segment 8 or 16.
* In this case, PV and END will flicker in display window, and the alarm
relay acts.
This controller does not have END order if program procedure are less
than 8 segments. In this case, please set next segment’s out=0, then
this program will be end in last set segment. Otherwise, it will proceed
8 or 16 segments.
4)
Linking function
PTN=1, Proceed pattern1, which contains 8 segments
PTN=2, Proceed pattern2, which contains 8 segments
PTN=0, linking proceed pattern 1 and 2 ,totally 16 segments
(Set PTN1 and PTN2 first, then set PTN=0)