HONEYWELL CORE DRIVE
62-0410—04
22
cF1
EEPROM
write Err
Internal EEPROM can not be programmed.
1. Press “RESET” key to the factory setting
2. Return to the factory.
cF2
EEPROM
read Err
Internal EEPROM can not be read.
1. Press “RESET” key to the factory setting
2. Return to the factory.
cd1
las sensor
Err
U-phase error
Reboots the power. If fault code is still displayed on the keypad
please return to the factory
cd2
lbs sensor
Err
V-phase error
Reboots the power. If fault code is still displayed on the keypad
please return to the factory
cd3
lcs sensor
Err
W-phase error
Reboots the power. If fault code is still displayed on the keypad
please return to the factory
AFE
PID Fbk
error
PID loss (ACI)
1. Check the wiring of the PID feedback
2. Check the PID parameters settings
ACE
ACI loss
ACI loss
1. Check the ACI wiring
2. Check if the ACI signal is less than 4mA
EF
External
fault
External Fault
1. Input EF (N.O.) on external terminal is closed to GND. Output
U, V, W will be turned off.
2. Give RESET command after fault has been cleared.
EF1
Emergency
stop
Emergency stop
1. When the multi-function input terminals MI1 to MI6 are set to
emergency stop, the AC motor drive stops output U, V, W and
the motor coasts to stop.
2. Press RESET after fault has been cleared.
bb
Base block External Base Block
1. When the external input terminal (B.B) is active, the AC
motor drive output will be turned off.
2. Deactivate the external input terminal (B.B) to operate the AC
motor drive again.
Pcod
Password
error
Password is locked.
Keypad will be locked. Cycle power OFF and then ON to re-
enter the correct password. See Pr.00-07 and 00-08.
ccod
SW Code
Error
Software code error
CE1
PC Err
command
Illegal function code
Check if the function code is correct (function code must be 03,
06, 10, 63)
CE2
PC Err
address
Illegal data address (00H to 254H)
Check if the communication address is correct
CE3
PC Err data Illegal data value
Check if the data value exceeds max./min. value
CE4
PC slave
fault
Data is written to read-only address
Check if the communication address is correct
CE10 PC time out Modbus transmission time-out
CP10 Keypad time
out
Keypad transmission time-out
dEb
Dec Energy
back
When Pr07-12 is not set to 0 and momentary
power off or power cut, it will display dEb
during accel./decel. stop.
1. Set Pr07-12 to 0
2. Check if input power is stable
S1
S1-emergy
stop
Emergency stop for external safety
Fire
On Fire
Fire Mode
Uoc,
Voc,
Woc
A, B, or C
phase short
Phase A, B, or C short circuit
OPHL
U, V, or W
phase
lacked
Output phase loss (Phase U), (Phase V), (phase W)
Table 14. Fault Codes and Descriptions
NOTE: Additional details and screen shots of the error messages can be found in the full manual.