HONEYWELL CORE DRIVE
3
62-0410—04
ENVIRONMENT FOR OPERATION, STORAGE AND
TRANSPORTATION
DO NOT expose the VFD to an improper environment, such as dust, direct sunlight, corrosive/inflammable gases,
humidity, liquid and vibration environment. The salt in the air must be less than 0.01mg/cm
2
every year.
* HD = Heavy Duty, higher overload rating. ND = Normal Duty, Standard HVAC applications
NOTE: To prevent personal injury, please make sure that the case and wiring are installed according to this instruc-
tion. The figures in this instruction are only for reference, they may be slightly different from the one you have
but it will not affect your customer rights. The installation instruction may revise without prior notice. Please
refer to our distributors or download the updated version at http://www.customer.honeywell.com/VFD.
Environ
ment
Installation location IEC60364-1/IEC60664-1 Pollution degree 2, Indoor use only
Surrounding
Temperature
Storage: -25
o
C / -13
o
F ~ +70
o
C / 167
o
F
Transportation: -25
o
C / -13
o
F ~ +70
o
C / 167
o
F
Non-condensation, non-frozen
Rated Humidity
Operation: Max. 90%
Storage/Transportation: Max. 95%
No condensing water
Air Pressure
Operation/ Storage: 86 to 106 kPa Transportation: 70 to 106 kPa
Pollution Level
IEC721-3-3
Operation: Class 3C2; Class 3S2 Storage: Class 2C2; Class 2S2 Transportation: Class 1C2; Class 1S2
No concentrate
Conformal coated boards
Altitude
Operation
If VFD is installed at altitude 0~1000m, follow normal operation restriction. If it is installed
at altitude 1000~3000m, decrease 2% of rated current or lower 0.5
o
C of temperature for
every 100m increase in altitude. Maximum altitude for Corner Grounded is 2000m.
Package
Drop
Storage
ISTA procedure 1A(according to weight) IEC60068-2-31
Transportation
Vibration 1.0mm, peak to peak value range from 2Hz to 13.2 Hz; 0.7G~1.0G range from 13.2Hz to 55Hz; 1.0G range from 55Hz to
512 Hz. Comply with IEC 60068-2-6
Impact
IEC/EN 60068-2-27
Operation
Position
Max. allowed offset angle ±10
o
(under normal installation
position)
Plenum
Rating
Compliance with UL 508C, the Standard for Power Conversion Equipments, 3rd Edition, and the Canadian Standard for
Industrial Control Equipment, C22.2-No. 14.
Motor Cable Lengths
For Models 7.5HP/5.5kW and above:
Insulation Level of Motor
1000V
1300V
1600V
460VAC Input Voltage
66ft
328ft
1312ft
230VAC Input Voltage
1312ft
1312ft
1312ft
For Models 5HP/3.7kW and below:
Insulation Level of Motor
1000V
1300V
1600V
460VAC Input Voltage
66ft
165ft
165ft
230VAC Input Voltage
328ft
328ft
328ft
Model
Frame
Top cover
Conduit Box
Protection
Level
Operation
Temperature*
HCRDAxxxxx1000T
HCRDCxxxxx1000T
Frame A~C
230V: 0.75-33kW
1-40hp
460V: 0.75~37kW
1-50hp
Remove top
cover
Standard
conduit plate
IP20/UL Open
Type
HD: -10-50
o
C (14-120
o
F)
ND: -10-40
o
C (14-104
o
F)
Standard with
top cover
IP20/UL Type1/
NEMA1
HD: -10-40
o
C (14-104
o
F)
ND: -10-40
o
C (14-104
o
F)
Frame D~E
230V:
≥
37kW/50hp
460V:
≥
45kW/60hp
N/A
With conduit
box
IP20/UL Type1/
NEMA1
HD: -10-40
o
C (14-104
o
F)
ND: -10-40
o
C (14-104
o
F)