HONEYWELL CORE DRIVE
9
62-0410—04
SPECIFICATIONS FOR WIRING TERMINALS
Table 5. Specifications for Wiring Terminals
(refer to wiring diagram)
Control terminals
Main terminals
Wire Gauge: 26-16AWG. (0.1281-1.318mm
2
)
Torque (±10%): 5kg-cm[4.31 lb-in.] (0.49Nm), 5kg-cm[4.31 lb-in.] (0.49Nm)
Models VFD-
Max. Wire
Gauge
Min. Wire Gauge
Torque (±10%)
Note
HCRDA0010A1000T
8 AWG
(8.4mm
2
)
14 AWG (2.1mm
2
)
M4 20kg-cm
(17.4 lb-in.)
(1.962Nm)
HCRDA0020A1000T
14 AWG (2.1mm
2
)
HCRDA0030A1000T
12 AWG (3.3mm
2
)
HCRDA0050A1000T
10 AWG (5.3mm
2
)
HCRDA0075A1000T
10 AWG (5.3mm
2
)
HCRDC0010A1000T
14 AWG (2.1mm
2
)
HCRDC0020A1000T
14 AWG (2.1mm
2
)
HCRDC0030A1000T
14 AWG (2.1mm
2
)
HCRDC0050A1000T
14 AWG (2.1mm
2
)
HCRDC0075A1000T
10 AWG (5.3mm
2
)
HCRDC0100A1000T
10 AWG (5.3mm
2
)
HCRDA0100B1000T
4 AWG
(21.2mm
2
)
8 AWG (8.4mm
2
)
M5 35kg-cm
(30.4 lb-in.)
(3.4335Nm)
Terminal D+[+2 & +1]:
Torque 45 Kg-cm [39.0 lb-in.] (4.415Nm) (±10%)
Use 600V, 90
o
C wired for UL installation for
HCRDA0200B1000T install in ambient temperature
exceeds 40
o
C.
HCRDA0150B1000T
4 AWG (21.2mm
2
)
HCRDA0200B1000T
4 AWG (21.2mm
2
)
HCRDC0150B1000T
8 AWG (8.4mm
2
)
HCRDC0200B1000T
8 AWG (8.4mm
2
)
HCRDC0250B1000T
6 AWG (13.3mm
2
)
HCRDA0250C1000T
1/0 AWG
(53.5mm
2
)
1 AWG (42.4mm
2
)
M8 80kg-cm
(69.4 lb-in.)
(7.848Nm)
Terminal D+[+2 & +1]:
Torque 90 Kg-cm [78.2 lb-in.] (8.83Nm) (±10%)
Use 600V, 90
o
C wired for UL installation for
HCRDA0400C1000T install in ambient temperature
exceeds 40
o
C.
HCRDA0300C1000T
1/0 AWG (53.5mm
2
)
HCRDA0400C1000T
1/0 AWG (53.5mm
2
)
HCRDC0300C1000T
4 AWG (21.2mm
2
)
HCRDC0400C1000T
4 AWG (21.2mm
2
)
HCRDC0500C1000T
2 AWG (33.6mm
2
)
HCRDA0500D1000T
4/0 AWG
(107mm
2
)
4/0 AWG (107mm
2
)
M8 200kg-cm
(173 lb-in.)
(19.62Nm)
Use the specified insulated heat shrink tubing that
complies with UL (600C, YDPU2). Must use 90
o
C wire
for HCRDA0600D1000T & HCRCD1250D1000T.
HCRDA0600D1000T
4/0 AWG (107mm
2
)
HCRDC0600D1000T
1/0 AWG (53.5mm
2
)
HCRDC0750D1000T
2/0 AWG (67.4mm
2
)
HCRDC1000D1000T
4/0 AWG (107mm
2
)
HCRDC1250D1000T
4/0 AWG (107mm
2
)
HCRDA0750E1000T
4/0 AWG*2
(107mm2*2)
1/0 AWG*2
(53.5mm
2
*2)
M8 200kg-cm
(173 lb-in.)
(Figure 1) The usage of ring terminals should comply
with the specifications shows in the figure.
(Figure 2) Grounding wire specification: 300MCM*2
[152 mm2*2]
Torque M8 180Kg-cm [156 lb-in.] (17.64Nm) (±10%)
(Figure 3) The figure shows the specification of
insulated heat shrink tubing that complies with UL
(600C, YDPU2)
HCRDA1000E1000T
2/0 AWG*2
(67.4mm
2
*2)
HCRDA1250E1000T
3/0AWG*2
(85mm
2
*2)
WIRE
HEAT
SHRINK
TUBE
RING LUG
13 MIN.
17 MAX.
RING
LUG
28 MAX.
28 MAX.
8.2 MIN.
48 MAX.
M31492
M31491
FIGURE 1
26.5 MAX.
8.2 MIN.
31 MAX.
70 MAX.
16
+0
-4
17 MAX.
65 MAX.
8.2 MIN.
28 MAX.
FIGURE 2
WIRE
HEAT
SHRINK
TUBE
RING LUG
FIGURE 3
13 MIN.