Ch Item #
Item Name
Description
item 096 for both.
225
909
Ch1 Inc FixedFactor Volume
Ch2 Inc FixedFactor Volume
The Incremental FixedFactor Volumes are the
same as FixedFactor Volume (item 000 and 908)
but are initialized (re-zeroed) at the beginning of
every Log Interval (Hourly or Daily) as defined by
item 202. If the CNI4 is accessed via a serial
connection, this item will display the current value
for that point in time.
044
440
Ch1 FixedFactor Value
Ch2 FixedFactor Value
Default = 0.0000
User-assigned scaling factor to be applied to the
FixedFactor Volumes for Ch1 and Ch2. The
FixedFactor scaling is normally used to adjust the
accumulated volume for a fixed pressure factor, a
fixed temperature factor, or both. The scaling
factors default to a value of zero, which forces the
FixedFactor Volumes to remain at zero when the
fixed factor feature is not used.
092
090
Ch1 Accumulated Vol Units
Ch1 FixedFactor Vol Units
Select:
0 - CU FT
1 - CU FT x 10
2 - CRUFT x 100
3 - CF
4 - CF x 10
5 - CF x 100
6 - CF x 1000
7 - CCF (Default)
8 - MCF
9 - m3 x 0.1
10 - m3
11 - m3 x 10
12 - m3 x 100
13 - m3 x 1000
14 - CF x 10,000
15 - THERMS
16 - DKTHERMS
17 - MJOULES
18 - GJOULES19 - KILOCAL
19 - kWh
20 - CF x 100,000
Codes (0-20) for item 092 (Accumulated Vol
Units) and item 090 (FixedFactor Vol Units) that
selects the volume units of measure.
097
096
Ch1 & Ch2 Accumulated Vol Digits
Ch1 & Ch2 FixedFactor Vol Digits
Select:
0 - 8 DIGITS, Example: 12345678
1 - 7 DIGITS, Example: 2345678
2 - 6 DIGITS, Example: 345678
3 - 5 DIGITS, Example: 45678
4 - 4 DIGITS, Example:5678
Codes (0-4) for items 097 (Accumulated Vol
digits) and 096 (FixedFactor Vol Digits) that
selects the number of digits when displaying
either type of volume reading.
9 Appendix
Honeywell
| 53