Ch Item #
Item Name
Description
261
Audit Trail Data Item 4 of 10
Default: 911 (Ch2 Inc.
Accumulated Volume)
229
Audit Trail Data Item 5 of 10
Default: 255 (blank)
230
Audit Trail Data Item 6 of 10
Default: 255 (blank)
231
Audit Trail Data Item 7 of 10
Default: 255 (blank)
232
Audit Trail Data Item 8 of 10
Default: 255 (blank)
233
Audit Trail Data Item 9 of 10
Default: 255 (blank)
234
Audit Trail Data Item 10 of 10
Default: 255 (blank)
9.1.6 Alarm Items
Ch Item #
Item Name
Description
099
Battery Low Volt
Alarm
Default = 00000000
This item indicates if a low voltage alarm for the main battery
was generated. During a wake-cycle, if the measurement for
item 048 (Battery Voltage Reading) is a value less than the
value at item 049 (Battery Low Volt Limit), an alarm is initiated
and is indicated by placing “11111111” at this item. “00000000”
indicates there is no Battery Low Volt Alarm. The alarm
indication cannot be cleared until the batteries are replaced or
the voltage becomes greater than item 049..
108
Alarm Output
Default = 00000000
This item displays “11111111” to indicate that a Battery Low
Volt Alarm has become active, and that an alarm pulse was
transmitted out the Alarm Channel. “00000000” at item 108
indicates there are no active alarms.
462
Battery Low Alarm
Time
Default = 00 00 00
The time during the day (on the date indicated at item 463) the
Battery Low Volt Alarm occurred.
463
Battery Low Alarm
Date
Default = 01-01-04
The date a Battery Low Volt Alarm (item 099) first occurred.
After the battery pack is replaced, items 462 and 463 should be
manually changed back to their default values so that the next
battery alarm will be easily recognized
484
Alarm Channel
Control
Select:
0 - Alarm Pulse
Selection that determines the function of the main board’s
Alarm Channel output, i.e., terminals A+ & A- at TB1. The
traditional function is to output a 50 mSec Form-A alarm pulse,
used for remote notification. The alternative function is to
9 Appendix
Honeywell
| 58