Select the check-box next to an Item number, enter a value in the text box provided and then
click on Write Item button to write the value against the item in the connected
instrument/device. You can search for a specific item number and can also modify multiple
Item Numbers at once. You can also use the Read Item button (enabled only when an item is
selected) to read the currently configured value of the item numbers.
Set the following parameters:
Item No.
Description
Recommended Value
333
Call-in Trigger
3 = Alarm & Scheduled Call-in
449
Switch Filtering
1 = Filter Both Channels
486
Modem AT-Command Enable
1-Yes
334
Scheduled Call-In Date
Set to the desired Call-In Date
335
Scheduled Call-In Time
Set to the desired Call-In Time
336
Call-In Retry By
Instrument
339
Scheduled Call-In Phone number
<IP>/<Port>Example:
192.168.1.1/50467
485
Call-Out Stop Time
00:00:00
490
Call-Out Start Time
00:00:00
493
Alarm Call-In Phone number
<IP>/<Port> Example:
192.168.1.1/50467
495
Modem Retry Interval A
5 minutes
496
Modem Retry Interval B
1440 minutes
497
Modem Retry A Count
3
12. Click Disconnect to disconnect MasterLink from the Pulse Accumulator. On successful
disconnection from the Pulse Accumulator, a status message is displayed. Close the pop-up to
acknowledge the message.