background image

LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA 

EN0Z-0959GE51 R0615 

14 

CHECKOUT 

Step 1. Check Installation and Wiring 

Inspect all wiring connections at the controller terminals, and 
verify compliance with installation wiring diagrams. If any 
wiring changes are required, 

first 

be sure to remove power 

from the controller 

before 

starting work. Pay particular 

attention to: 

  24 Vac power connections. Verify that multiple controllers 

being powered by the same transformer are wired with the 
transformer secondary connected to the same input 
terminal numbers on each controller. Use a meter to 
measure 24 Vac at the appropriate terminals (see Fig. 
10). Controller configurations are not necessarily limited to 
three devices, but the total power draw, including 
accessories, cannot exceed 100 VA when powered by the 
same transformer (U.S., only). 

  Ensure that each controller has terminal 3 wired to a 

verified earth ground, using a wire run as short as possible 
with the heaviest gauge wire available, up to 2.0 mm

2

 with 

a min. of 1.0 mm

2

 for each controller in the group (see Fig. 

10). 

  Check that the MS/TP network polarity has been con-

nected properly on each controller. BACnet MS/TP is 
polarity sensitive; communication will be lost for the entire 
segment if one controller is connected improperly (see 
Fig. 11). 

  Verify that triac wiring of the digital outputs to external 

devices uses the proper load power and 24 Vac common 
terminal (digital output common terminals) for high-side 
switching. 

NOTE:

 

All wiring must comply with applicable electrical 
codes and ordinances or as specified on 
installation wiring diagrams. 

For guidelines for wiring run lengths and power budget, see 
section “Power” on page 6. 
 

Verify End-of-Line Termination Resistor Placement 

The installation wiring diagrams should indicate the locations 
for placement of the end of line termination resistors. See Fig. 
11. 
Correct placement of the end-of-line termination resistors is 
required for proper BACnet MS/TP Bus communications. 
 

Step 2. Startup 

See Fig. 20 and the following text for startup information. 
 

CLLYVB6438NS

DO-

1

DO-

2

DO-

4

DO-

6

DO-

8

COM

COM

COM

COM

DO-

3

DO-

5

DO-

7

BAC

+

BAC

-

24V

AC

20VDC

EGN

D

S-

BUS

S-

BUS

24

VA

C

 CO
M

AO
-1

DI

-1

DI

-2

AO
-2

AO
-3

CO
M

CO
M

CO
M

DI

-3

DI

-4

20

VD

C

UI

-1

CO
M

UI

-2

UI

-3

CO
M

UI

-4

UI

-5

CO
M

UI

-6

BACnet MS/TP MAC

ADDRESS DIP SWITCHES

LOCAL BACnet MS/TP

MOLEX CONNECTOR PINS

HOST

STATUS

LED

21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

1

3 4 5 6

2

7 8

9 10 11 12 13 14 15 16 17 18 19 20

 

Fig. 20. LED, service, network, and terminal connections 

(CLLYVB6438NS shown) 

 

Set the MS/TP MAC Address 

The MS/TP MAC address DIP switches are used to set the 
unit's MAC address. Each LYNX controller on an MS/TP 
network must have a unique MAC address in the range of 0-
127 (address 0 should be avoided as it is the Honeywell 
factory default MAC address for all MS/TP devices). 
 

Controller Status LED 

The LED on the front of the controller provides a visual 
indication of the status of the device. When the controller 
receives power, the LED appears in one of the following 
allowable states, as described in Table 6. 

Table 6. Status LED states 

LED state 

blink rate 

status or condition 

OFF 

not applicable 

No power to CPU, LED 
damaged, low voltage to 
board, first sec of power-up, or 
loader damaged. 

ON ON 

steadily, 

not 

blinking 

CPU not operating. Application 
Program CRC being checked. 
This takes 1-2 sec and occurs 
on each restart (power-up, 
reset, and reflash, and 
following configuration file 
download). 

very slow 
blink (con-
tinuous) 

1 sec ON, 1 sec 
OFF 

Controller is operating 
normally. 

slow blink 
(continuous) 

0.5 sec ON, 0.5 
sec OFF 

Controller alarm is active or 
controller in process of con-
figuration file download. 

medium 
blink (con-
tinuous) 

0.3 sec ON, 0.3 
sec OFF 

Controller is in reflash mode or 
awaiting / receiving reflash 
data via BACnet. 

 

BACNET Status LED 

The LED on the front of the controller, between the BACnet 
MS/TP terminals and MAC Address DIP Switches, provides a 

Содержание CentraLine LYNX BACnet CLLYUB1012S

Страница 1: ...nications Each controller has flexible universal inputs for wall modules digital inputs and a mix of analog and digital triac outputs see Table 1 The models CLLYVB6436AS CLLYVB0000AS and CLLYVB4022AS include an actuator Table 1 Controller configurations model type Universal Inputs UI Digital Inputs DI Analog Out puts AO Digital Out puts DO velocity pressure sensor Microbridge floating actuator CLL...

Страница 2: ... Analog voltage outputs Voltage output range 0 10 Vdc Max output current 10 0 mA UNIVERSAL INPUT UI CIRCUITS See Table 2 for UI circuit specifications Table 2 Universal input circuit specifications input type sensor type operating range Room Zone Discharge Air Outdoor Air Temp NTC 20kOhm 40 93 C Outdoor Air Temperature PT1000 IEC751 3850 40 93 C Resistive Input Generic 100 Ω 100 kΩ Voltage Input T...

Страница 3: ...ersal shaft adapter see Fig 1 UNIVERSAL SHAFT CLAMPING BOLTS 2 UNIVERSAL SHAFT ADAPTER MECHANICAL END LIMIT SET SCREWS 2 DECLUTCH BUTTON Fig 1 Floating actuator IMPORTANT Determine the damper rotation and opening angle prior to installation See Fig 2 and Fig 3 for examples DAMPER DAMPER SHAFT ROTATES CW TO OPEN Fig 2 Damper with 90 clockwise rotation to open IMPORTANT Mount actuator flush with dam...

Страница 4: ...gether to reduce the rotation travel c Tighten the two mechanical end limit screws Phillips 2 screwdriver 3 0 3 5 Nm torque d Using the DECLUTCH button rotate the universal shaft adapter fully CCW e Mount the actuator to the VAV damper box and shaft f Tighten the two bolts on the centering clamp 8 mm wrench 8 10 Nm torque g When the actuator closes the damper rotates CW either 45 or 60 to fully cl...

Страница 5: ...10 11 12 13 14 15 16 17 18 19 20 9 10 11 12 13 14 15 16 17 18 19 20 Fig 6 Panel mounting dimensions in mm S and NS models NOTE The controller is designed so that the cover does not need to be removed from the base plate for either mounting or wiring The controller mounts using four screws inserted through the corners of the base plate Fasten securely with four screws The controller can be mounted ...

Страница 6: ...ionships early in the job engineering process to ensure proper implementation when configuring the controllers See the controller Application Guides Power Budget A power budget must be calculated for each device to deter mine the required transformer size for proper operation A power budget is simply the sum of the max power draw ratings in VA of all the devices to be controlled This includes the ...

Страница 7: ...wiring recommendations see section Power on page 6 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 9 9 OUTPUT DEVICE POWER TRANSFORMER 120 240 VAC COM 24 VAC EARTH GROUND TERMINAL 3 EARTH GROUND TERMINAL 3 EARTH GROUND TERMINAL 3 EARTH GROUND WHEN CONNECTING POWER TO THE LYNX BACnet CONTROLLER CONNECT THE COM LEG OF THE VAC SECONDARY CIRCUIT TO A KNOWN EARTH GROUND CONNECT POWER TO TERMINALS 1 A...

Страница 8: ...e rated characteristic impedance of the installed cable E g if the installed MS TP cable has a listed characteristic impedance of 120 Ω install 120 Ω matched precision resistors NOTE LYNX controllers do not provide network biasing Shield Terminating Following proper MS TP cabling shield grounding procedures is important to minimize the risk of communication problems and equipment damage caused by ...

Страница 9: ...t present The actuator is internally hardwired to these terminals C Analog outputs may be configured as digital outputs and operate as follows FALSE 0 0 Vdc 0 mA TRUE 100 the max 11 Vdc 22 mA D Digital inputs open circuit FALSE closed circuit TRUE UI 1 is selectable as a fast digital pulse meter Table 5 Description of wiring terminals CLLYVB0000AS CLLYVB4022AS and CLLYVB6436AS TERMINAL LABEL CONNE...

Страница 10: ...gital inputs see Fig 17 Typical controller wiring for 4 20 mA heating cooling and model ML6161 floating motor control see Fig 18 Typical controller wiring for a pneumatic transducer model RP7517B see Fig 19 24VAC BACnet MS TP BACnet MS TP SHIELD 24VAC COM REHEAT STAGE 3 REHEAT STAGE 2 OR CLOSE REHEAT STAGE 1 OR OPEN DAMPER CLOSE DAMPER OPEN C770A AIR TEMP SENSOR AIR FLOW PICK UP WINDOW CONTACTS CO...

Страница 11: ...LVE ACTUATOR PWM VALVE ACTUATOR PWM OUTPUT FROM CONTROLLER PWM H 24 VAC T5 T6 C B W R 24 N 24 H 2 3 3 3 2 1 3 4 ON OFF ML7984B CONFIGURATION DIP SWITCHES LOCATED ADJACENT TO THE INPUT TERMINAL BLOCK PERIPHERAL HEAT VALVE ACTUATOR ML7984B REHEAT VALVE ACTUATOR CLLYUB6438S DO 1 DO 2 DO 4 DO 6 DO 8 COM COM COM COM DO 3 DO 5 DO 7 BAC BAC 24VAC 20VDC EGND S BUS S BUS 24VAC COM AO 1 DI 1 DI 2 AO 2 AO 3 ...

Страница 12: ...her 4 20 mA signal devices Place this resistor as close as possible to the driven device CLCM4T111 WALL MODULE GND SENSOR SET POINT BYPASS LED 5 6 7 4 3 2 1 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 4 1 2 3 4 5 6 7 8 1 1 1 1 1 1 1 1 1 1 2 1 2 3 4 5 6 7 8 9 0 0 9 CLLYUB6438S 24 VAC 24 VAC COM E GND SHLD SBUS1 SBUS2 NET 1 NET 2 DO 1 DO 2 COM COM COM COM DO 3 DO 4 ...

Страница 13: ...g diagram CLLYUB6438S shown with 4 20 mA heating cooling and ML6161 damper actuator NOTE 1 Earth ground wire length should be held to a minimum Use the heaviest gauge wire available up to 14 AWG 2 0 mm 2 with a minimum of 18 AWG 1 0 mm 2 for earth ground wire NOTE 2 Ensure that all transformer power wiring is as shown Reversing terminations will result in equipment malfunction 1 2 3 4 5 6 7 8 9 0 ...

Страница 14: ...ee Fig 11 Correct placement of the end of line termination resistors is required for proper BACnet MS TP Bus communications Step 2 Startup See Fig 20 and the following text for startup information CLLYVB6438NS DO 1 DO 2 DO 4 DO 6 DO 8 COM COM COM COM DO 3 DO 5 DO 7 BAC BAC 24VAC 20VDC EGND S BUS S BUS 24VAC COM AO 1 DI 1 DI 2 AO 2 AO 3 COM COM COM DI 3 DI 4 20VDC UI 1 COM UI 2 UI 3 COM UI 4 UI 5 C...

Страница 15: ...vere injury death or property damage Do not attempt to modify the physical or electrical characteristics of this device in any way If trouble shooting indicates a malfunction replace the controller WARNING Electrical Shock Hazard Can cause severe injury death or property damage To prevent electrical shock or equipment damage disconnect power supply before beginning controller replacement Terminal ...

Страница 16: ... proceed as follows 1 Remove all power from the controller 2 Remove the two air flow pickup connections from the pressure sensor 3 Remove the terminal blocks see section Terminal Block Removal 4 Remove the old controller from its mounting IMPORTANT IN THE CASE OF CONTROLLERS MOUNTED TO A DIN RAIL 1 Push straight up from the bottom to release the top pins 2 Rotate the top of the controller outwards...

Отзывы: