C7660 SELECTABLE TEMPERATURE SENSOR

® U.S. Registered Trademark
© 2008 Honeywell International Inc.
63-2670EF—01 M.S. 09-08 

The changeover temperature switch settings for the C7660 

are shown in Fig. 3. Default and factory setpoint is 63° F. 

Changeover on an economizer can operate in two basic 

modes: 

1) exclusive operation where either the economizer or the 

mechanical cooling function, but not both OR 

2) integrated operation where the economizer and mechanical 

cooling operate at the same time. Integrated operation 

requires a two stage cooling thermostat. The integrated 

control will provide the most energy savings.

For exclusive operation, the changeover set point needs to 

allow mechanical cooling when the economizer can no longer 

meet the cooling load requirement. The 63 degree F setting is 

the most typical changeover set point for this type of control 

but is dependent on the building and climate.

For integrated operation, the changeover should be just at or 

just below the typical cooling setpoint expected in the zone 

served. For example, if the cooling setpoint is 74 degrees F or 

75 degrees F, the changeover setpoint should be set at 73 

degrees F.

Fig. 3. C7660 Temperature Sensor Dip Switch Settings.

ON

OFF

1

3

2

78ºF

ON

OFF

1

3

2

73ºF

ON

OFF

1

3

2

68ºF

ON

OFF

1

3

2

63ºF

ON

OFF

1

3

2

58ºF

ON

OFF

1

3

2

55ºF

ON

OFF

1

3

2

53ºF

ON

OFF

1

3

2

48ºF

M27636

DIP SWITCH

POSITION

CHANGEOVER

TEMPERATURE

Содержание C7660

Страница 1: ...ses temperature of outdoor air and provides a signal to economizer control with OK or not OK to economize Selectable dip switch provides 8 change over temperature options When temperature of outdoor air is below change over temperature the outdoor air damper is opened to reduce the cooling load in the building Provides 4 OR 20 mA output signal to economizer control At 4 mA not OK to economize 20 m...

Страница 2: ...ze Operating Ambient Temperature Range 40 to 149 F 40 to 65 C Shipping Temperature Range 40 to 149 F 40 to 65 C Supply Voltage Power to sensor is supplied through economizer or if not used with an economizer logic power input is 21 6 vdc 1 5 vdc Electrical Connections Two 1 4 in 6 4 mm quick connect terminals Approval Underwriters Laboratories Inc Flammability Rating UL94 5V Dimensions See Fig 1 H...

Страница 3: ...below the change over setpoint the sensor will provide a 20 mA signal to the economizer with translate to OK to economize positioning the damper open on a call for cooling When the outdoor air is above the change over setpoint the sensor provides a 4 mA signal to the economizer which translates to not OK to economize and the outdoor damper drives to minimum position The C7660 temperature sensors r...

Страница 4: ...rated operation requires a two stage cooling thermostat The integrated control will provide the most energy savings For exclusive operation the changeover set point needs to allow mechanical cooling when the economizer can no longer meet the cooling load requirement The 63 degree F setting is the most typical changeover set point for this type of control but is dependent on the building and climat...

Страница 5: ...nal à l économiseur lui indiquant s il convient ou non de passer en mode économiseur Commutateurs DIP offrant 8 choix de températures d inversion Quand la température de l air extérieur est inférieure à la température d inversion le registre d admission d air frais est ouvert afin de réduire la charge de refroidissement du bâtiment Transmet un signal de 4 OU 20 mA à l économiseur à 4 mA le système...

Страница 6: ...à 149 F Température à l expédition 40 à 65 C 40 à 149 F Tension d alimentation Le capteur est alimenté en courant par l économiseur ou s il n est pas employé avec un économiseur l alimentation logique sera de 21 6 V c c 1 5 V c c Raccordement électrique Deux bornes à connexion rapide de 6 4 mm 1 4 po Approbation Laboratoire des assureurs Inc Indice d inflammabilité UL9 5V Encombrement Voir la Fig ...

Страница 7: ...met à l économiseur un signal de 20 mA que celui ci traduit comme une commande de mise en service de l économiseur il positionne alors le registre à la position d ouverture lors d une demande de refroidissement Quand le capteur extérieur détecte une température supérieure au point de consigne le capteur transmet un signal de 4 mA à l économiseur que celui ci interprète comme une commande de ne pas...

Страница 8: ...d inversion doit permettre le refroidissement mécanique lorsque l économiseur ne suffit plus à répondre à la charge de refroidissement Le réglage de 63 F est le point d inversion le plus fréquent pour ce type de régulation le réglage dépend toutefois du bâtiment et du climat Pour un fonctionnement intégré le point de consigne d inversion doit être réglé au point de consigne de refroidissement type...

Отзывы: