C7660 SELECTABLE TEMPERATURE SENSOR

3

63-2670EF—01

Fig. 2. Wiring Connections for C7660 Temperature Sensor.

CAUTION

1. Before beginning installation, disconnect power 

supply to prevent electrical shock or equipment 

damage.

2. When selecting the location, make sure the 

sensor is not exposed to rain, snow or direct 

sunlight.

Location

The C7660 Temperature Sensor can be mounted in any 

position; however, the sensor must be installed where it is 

exposed to freely circulating air but protected from rain and 

direct sunlight.

Wiring

Disconnect power supply before beginning installation to 

prevent electrical shock or equipment damage. All wiring must 

comply with applicable codes and ordinances. Follow the 

wiring information furnished by the equipment manufacturer or 

see Fig. 2 for typical wiring hookups.

OPERATION

Temperature Change Over Control Setting

The temperature change over setpoint is made by changing 

the setting on a 3-position dip switch through the cover of the 

sensor. See Fig. 3 for temperature change over settings.

Operation

The C7660 Selectable Temperature Sensor is used with an 

economizer control and damper actuator to proportion an 

outdoor air damper in a ventilation system. 

When outdoor air temperature is below the change over 

setpoint, the sensor will provide a 20 mA signal to the 

economizer with translate to 

OK to economize

 positioning the 

damper open on a call for cooling. When the outdoor air is 

above the change over setpoint, the sensor provides a 4 mA 

signal to the economizer which translates to 

not OK to 

economize

 and the outdoor damper drives to minimum 

position.

The C7660 temperature sensors replace the control function of 

the temperature changeover in the economizer control.

The A, B, C, D potentiometer on the economizer does not 

control the changeover point when a C7660 sensor is used in 

place of an enthalpy sensor. This potentiometer is only 

adjusted when using a C7400 enthalpy sensor for single 

enthalpy changeover. For single dry-bulb and differential 

enthalpy set the potentiometer to “D”.

L1 

(HOT)
L2

1

1

TR1

TR

+

+

+

5

2

4

T1

P1

SO

SR

1

3

T

P

620 OHM

RESISTOR

C7660 OUTDOOR

AIR TEMPERATURE

SENSOR

A

B

C

D

TEMPERATURE

SETPOINT

OPEN

MINIMUM

POSITION

MINIMUM

POSITION

24 Vac

MIXED AIR

SENSOR

TR

TR1

TR

TR1

TR

TR1

SEE W7459 SPECIFICATIONS FOR ADDITIONAL WIRING INFORMATION.

POLARITY OF SENSOR IS REQUIRED TO C ON SENSOR TO + ON ECONOMIZER AND – ON SENSOR TO SO ON ECONOMIZER.

ONLY ONE C7660 SENSOR CAN BE USED WITH AN ECONOMIZER FOR SINGLE DRY-BULB CHANGEOVER. DO NOT USE A SECOND

C7660 SENSOR ON THE SR AND SR+ TERMINALS.

W7459 ECONOMIZER PACKAGE MOUNTED ON ACTUATOR

W7459 ECONOMIZER PACKAGE

ACTUATOR

M27635

2

3

2

3

Содержание C7660

Страница 1: ...ses temperature of outdoor air and provides a signal to economizer control with OK or not OK to economize Selectable dip switch provides 8 change over temperature options When temperature of outdoor air is below change over temperature the outdoor air damper is opened to reduce the cooling load in the building Provides 4 OR 20 mA output signal to economizer control At 4 mA not OK to economize 20 m...

Страница 2: ...ze Operating Ambient Temperature Range 40 to 149 F 40 to 65 C Shipping Temperature Range 40 to 149 F 40 to 65 C Supply Voltage Power to sensor is supplied through economizer or if not used with an economizer logic power input is 21 6 vdc 1 5 vdc Electrical Connections Two 1 4 in 6 4 mm quick connect terminals Approval Underwriters Laboratories Inc Flammability Rating UL94 5V Dimensions See Fig 1 H...

Страница 3: ...below the change over setpoint the sensor will provide a 20 mA signal to the economizer with translate to OK to economize positioning the damper open on a call for cooling When the outdoor air is above the change over setpoint the sensor provides a 4 mA signal to the economizer which translates to not OK to economize and the outdoor damper drives to minimum position The C7660 temperature sensors r...

Страница 4: ...rated operation requires a two stage cooling thermostat The integrated control will provide the most energy savings For exclusive operation the changeover set point needs to allow mechanical cooling when the economizer can no longer meet the cooling load requirement The 63 degree F setting is the most typical changeover set point for this type of control but is dependent on the building and climat...

Страница 5: ...nal à l économiseur lui indiquant s il convient ou non de passer en mode économiseur Commutateurs DIP offrant 8 choix de températures d inversion Quand la température de l air extérieur est inférieure à la température d inversion le registre d admission d air frais est ouvert afin de réduire la charge de refroidissement du bâtiment Transmet un signal de 4 OU 20 mA à l économiseur à 4 mA le système...

Страница 6: ...à 149 F Température à l expédition 40 à 65 C 40 à 149 F Tension d alimentation Le capteur est alimenté en courant par l économiseur ou s il n est pas employé avec un économiseur l alimentation logique sera de 21 6 V c c 1 5 V c c Raccordement électrique Deux bornes à connexion rapide de 6 4 mm 1 4 po Approbation Laboratoire des assureurs Inc Indice d inflammabilité UL9 5V Encombrement Voir la Fig ...

Страница 7: ...met à l économiseur un signal de 20 mA que celui ci traduit comme une commande de mise en service de l économiseur il positionne alors le registre à la position d ouverture lors d une demande de refroidissement Quand le capteur extérieur détecte une température supérieure au point de consigne le capteur transmet un signal de 4 mA à l économiseur que celui ci interprète comme une commande de ne pas...

Страница 8: ...d inversion doit permettre le refroidissement mécanique lorsque l économiseur ne suffit plus à répondre à la charge de refroidissement Le réglage de 63 F est le point d inversion le plus fréquent pour ce type de régulation le réglage dépend toutefois du bâtiment et du climat Pour un fonctionnement intégré le point de consigne d inversion doit être réglé au point de consigne de refroidissement type...

Отзывы: