Installation Guide

60-2104—01 6

INSTALLATION

When Installing This Product 

1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a hazardous 
condition.
2. Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check product operation 
as provided in these instructions.

WARNING

Explosion Hazard.

Can cause serious injury, death or property 

damage. This product is intended for use only 
in systems with a pressure relief valve.

WARNING

Electrical Shock Hazard.

Can cause serious injury or death. Disconnect 

power supply before beginning installation to 

prevent electrical shock or equipment dam-
age.

CAUTION

Equipment Damage Hazard.

Use of incorrect device or improper installa-

tion can damage the system.

1. Do not replace immersion-type Aquastat 

Controller with strap-on Aquastat Controller.

2. Do not secure draw nut so tightly that 

retainer clamp can collapse tubing.

IMPORTANT
1. Terminals on these Aquastat relays are approved for 

copper wire only. 

2. Controller may be used with or without immersion well. If 

used, well must snugly fit sensing bulb for best thermal 

response. Insert bulb until it rests against the bottom of 

the well. Use well of correct length and bend the tubing, 

if necessary, to provide enough force to hold the bulb 

against the bottom of the well. Avoid making a sharp 

bend in the tubing as it can produce a break in the 

tubing and cause loss of fill. This condition causes the 
High and Low Limit controls to be made continuously. 

3. If well does not snugly fit on bulb, use the heatconductive  

compound, included with Super Tradeline and Tradeline 

models, as follows: Fold the plastic bag of compound 

lengthwise and twist gently. Snip the end of the bag 

and insert into the well. Slowly pull out the bag while 

squeezing firmly to distribute compound evenly in the 

well. Insert the bulb into the well. Bend the tubing, if 

necessary, to provide force to hold the bulb against the 

bottom of the well and to hold the outer end of the bulb 

firmly in contact with the side of the well. Wipe off excess 

compound 

Accessories and Parts:

137536A Scale Lock Assembly: Includes one 137536-767 Scale Lock and one 80844C-767 Screw, No. 3-48 x 3/16 (5 mm).

Q615A1004 Weatherproof Enclosure (for remote bulb devices only).

107408 Heat-Conductive Compound (4-oz. can).

104488 Spring Clip (stainless steel).

124904 Well Adapter.

Immersion Well Assemblies and Compression Fittings:

See form no. 68-0040, Wells and Fittings for Temperature Controllers, for list and ordering information

APPROVALS

ACCESSORIES AND PARTS

Approvals:

Underwriters Laboratories Inc: 

Remote bulb devices and well-mounted devices shipped without well are component recognized: 

File No. MP466, Guide No. MBPR2.  

L4006A shipped with well, L4006G, L4007A,B; L6006C for surface mounting, L6006B for direct immersion mounting, and 

L6007A are listed: File No. MP466, Guide No. MBPR.
L6008G is listed: File No. E4436, Guide No. XAPX Canadian Standards Association: File No. LR1620, Guide No. 400-E-O.
ANSI Miswiring: Models with 1/4 in. (6.35 mm) tab terminal meet ANSI Appliance Miswiring Standard.
Finish: Gray.

1

The manufacturer usually provides a tapping for insertion 

of the controller sensing element. This tapping is located at 

a point where typical water temperature can be measured. 

Depending on the model, the element is inserted in an 

immersion well, through a boiler fitting, or directly immersed.
Installation should be made by a qualified service technician. 

Follow the instructions furnished by the system manufaturer, 

if available. Otherwise, refer to appropriate procedure listed 

below.

Содержание Aquastat L4006

Страница 1: ...ntrollers Aquastat Installation Guide GENERAL Aquastat Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers storage tanks and other applications where temperature control is required ...

Страница 2: ...e ordering number If you have additional questions need further information or would like to comment on our products or services please write or phone 1 Your local Honeywell Automation and Control Products Sales Office check white pages of your phone directory 2 Honeywell Customer Care 1885 Douglas Drive North Minneapolis Minnesota 55422 4386 In Canada Honeywell Limited Honeywell Limitée 35 Dynami...

Страница 3: ...so this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed SUPER TRADELINE TRADELINE MODELS SUPER TRADELINE controls offer features not available on TRADELINE or standard models and are designed to replace a wide range of Honeywell and competitive controls TRADELINE models are selected and p...

Страница 4: ...le Insulation depth 1 1 2 in or 3 in 38 mm or 76 mm NPT brass spud 3 4 in 19 mm Screw in front of case on dial sui able for Powerpile control Factory set stop at 240 F 116 C L4006C High or low limit 65 F to 200 F 18 C to 93 C 3 1 2 F 2 C fixed Horizontal direct immersion Breaks TRADELINE model available Less cover Capillary 10 in 254 mm NPT brass spud 3 4 in 19 mm L4006Eb High limit 130 F to 290 F...

Страница 5: ...irect immersion Breaks Remote capillary 5 1 2 ft 1 7 m 8 1 2 ft 2 6 m or 10 ft 3 0 m Factory set scale stops at 120 170 or 200 F 49 77 or 93 C Celsius scale markings Front cover screw L4008B Circulator 100 F to 240 F 38 C to 116 C 5 F 3 C fixed or 5 F to 30 F 3 C to 17 C adjustable Remote bulb direct immersion Makes Capillary 5 1 2 ft 1 7 m L4008Eb High limit 40 F to 80 F 4 C to 27 C or 130 F to 2...

Страница 6: ... 18 C to 93 C 5 F 3 C fixed or 5 F to 30 F 3 C to 17 C adjustable Horizontal or vertical surface mounted TRADELINE model available Strap on surface mount L6007A Circulator and low limit or high limit 40 F to 180 F 4 C to 82 C Fixed Horizontal or vertical Insulation depth 1 1 2 in or 3 in 38 mm or 76 mm L6008A Circulator and low limit cooling 100 F to 240 F 38 C to 116 C or 30 F to 70 F 35 C to 21 ...

Страница 7: ...ect insertion models Fig 2 Approximate installation dimensions in inches mm for remote bulb models Otherdimensions are the same as Fig 1 M8957A KNOCKOUT FOR 3 4 19 CONDUIT ON ALL MODELS SIMILAR KNOCKOUT ON BOTTOM FOR HORIZONTAL INSERTION AND REMOTE BULB MODELS 1 25 5 16 8 2 51 2 1 8 54 5 5 8 136 1 7 8 48 3 16 5 RESET BUTTON L4006E L4008E ONLY KNOCKOUT FOR 3 4 19 CONDUIT ON VERTICAL INSERTION MODEL...

Страница 8: ...deline models as follows Fold the plastic bag of compound lengthwise and twist gently Snip the end of the bag and insert into the well Slowly pull out the bag while squeezing firmly to distribute compound evenly in the well Insert the bulb into the well Bend the tubing if necessary to provide force to hold the bulb against the bottom of the well and to hold the outer end of the bulb firmly in cont...

Страница 9: ...m the boiler tapping 3 Install the immersion well included with the controller If the boiler tapping is greater than 1 2 in 13 mm use a reduction fitting to adapt the boiler opening to the 1 2 in 13 mm threads that are standard with the well or fitting Fittings with 3 4 in 19 mm threads are also available 4 Fill the system Make sure that the well is screwed intightly enough to prevent leakage Do n...

Страница 10: ...er itself or in the feed riser about 6 in 153 mm above the boiler If the riser is valved the bulb can be installed between the boiler and the valve NOTE Do not make sharp bends or kinks in the capillary Make bends no sharper than 1 in 25 mm radius After installing the controller carefully coil the excess capillary at the bottom of the controller case 1 M8777B WELL BULB SPUD MOUNTING CLAMP A DRAW N...

Страница 11: ...Capillary Compression Fitting 1 Screw the fitting into the boiler or pipe tapping 2 Place the packing nut on the tubing 3 Slide the bulb completely through the fitting 4 Place the composition disk and four slotted brass washers on the tubing in the order shown in Fig 11 Turn the brass washers so the slots are 180 degrees apart 5 Slide the seal assembly into the fitting and tighten the packing nut ...

Страница 12: ...r other debris cannot obstruct circulation of air around it and where children cannot reach it Avoid vents from the building Install the case at the indoor location selected fastening the screws through holes in the back of the case Bring out the bulb and tubing through a 3 4 in 19 mm hole in the outside wall avoiding sharp bends or kinks Leave excess tubing coiled near the case Do not make sharp ...

Страница 13: ...f the horizontal suction line between the coil and trap not on the trap 4 Attach the sensing bulb to the suction line with clips or straps See Fig 17 5 Coil the excess length of capillary tubing near the L6008A case 5 Coil the excess length of capillary tubing near the L6008A case Fig 16 Securing remote bulb in clip M8805B L6008A CIRCULATOR LOW LIMIT CONTROLLER CAPILLARY REMOTE BULB SUCTION LINE B...

Страница 14: ...OR AND LOW LIMIT CONTROLLER R W B M8780B COOLING EQUIPMENT INDICATING LIGHT Fig 21 L6008A used to control cooling equipment and indicating light Use with L4006A B L6008A Wiring Disconnect power supply before beginning installation to pre vent electrical shock or equipment damage All wiring must comply with local codes and ordinances regarding wire size type of insulation enclosure etc Figures 19 t...

Страница 15: ...nnection diagram for an oil fired hydronic heating system that provides year round domestic hot water using RA817A Fig 23 Typical oil fired hydronic heating system that provides year round domestic hot water using RA832A Use with L4006A B L6008A L1 HOT L2 1 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED WHEN USING CIRCULATOR LOW LIMIT CONTROL REMOVE L1 L2 JUMPER 2 L6...

Страница 16: ...BREAKS R W MAKES R B ON FALL BREAKS R W MAKES R B ON FALL INTERSTAGE DIFFERENTIAL DIFFERENCE BETWEEN THE TEMPERATURES AT WHICH THE TWO SWITCHES MAKE R W ADJUSTABLE FROM 3 F TO 10 F 1 7 C TO 5 6 C ON STANDARD MODELS OR FROM 3 6 F TO 12 F 2 0 C TO 6 7 C 55 F TO 175 F 13 C TO 79 C MODELS TWO SPDT SWITCHES OPERATE IN SEQUENCE EACH SWITCH DIFFERENTIAL IS FIXED AT APPROXIMATELY 3 F 1 7 C ON STANDARD MOD...

Страница 17: ... the wheel on the back of the snap switch See Fig 32 until the desired reading is aligned with the V notch in the frame The wheel provides an adjustment from 5 F to 30 F 3 C to 17 C Replace the cover on the Aquastat Controller 1 ADJUSTMENTS Adjust the control point to correspond with the boiler manufacturer recommendations To adjust insert a screwdriver in the slotted screw type head located benea...

Страница 18: ...8A case is located in a room with a lower temperature than the controlled space Adjusting the controlled space setting dial setting is necessary to compensate for the temperature difference of 35 F 20 C between the two rooms Table 3 indicates that the dial setting should be lowered 5 F 3 C to compensate for the 35 F 20 C temperature difference Manual Reset If the device includes manual reset L4006...

Страница 19: ...r Obtain medical atten tion if irritation develops and persists Ingestion Contact physician or local poison control center immediately Inhalation Remove patient to fresh Manufacturer Honeywell Inc 1985 Douglas Drive North Minneapolis MN 55422 Date Released October 8 1999 NFPA Ratings Health 0 Flammability 1 Reactivity 0 Personal Protection B Section 2 Composition Information on Ingredients Section...

Страница 20: ...e gloves and clothing are recommended as material is dif ficult to remove from skin and clothing Other Protective Equipment None required Section 9 Physical and Chemical Properties Appearance Odor Aluminum color semi solid material pleasant odor Solubility in Water Negligible Specific Gravity 0 86 Section 10 Stability and Reactivity Stability Stable Reactivity Hazardous polymerization will not occ...

Отзывы: