Installation Guide
60-2104—01 16
Table 3. Temperature Adjustments.
Difference Between Desired
Room Temperature and Case
Temperature
Reduce Dial Setting
°F
°C
°F
°C
0
0
-
0
5
3
3/4
.5
10
6
1-1/2
1
15
8
2
1
20
11
2-3/4
2
25
14
3-1/2
2
30
17
4-1/4
3
35
20
5
3
40
22
5-3/4
4
45
25
6-1/2
4
50
28
7
4
55
31
8
5
60
33
8-1/2
5
70
39
10
6
80
45
11-1/2
7
L6008A Location Differential Calibration
The L6008A1093 is calibrated for applications where the
bulb and controller case are located in the same control
space.
If the bulb and controller case are located in separate
rooms, and if the temperature in the two rooms is different,
an adjustment is required. Adjust the dial setting (control
space temperature setting) to compensate for the differ-
ence in temperature.
1. If the L6008A case is located in a room with a highern
temperature than indicated on the dial setting, raise the
dial setting the number of degrees listed in Table 3.
2. If the L6008A case is located in a room with a lower
temperature than indicated on the dial setting, lower the
dial setting the number of degrees listed in Table 3.
EXAMPLE:
In the example shown in Fig. 33, the L6008A case is located
in a room with a lower temperature than the controlled
space. Adjusting the controlled space setting (dial setting) is
necessary to compensate for the temperature difference of
35° F (20° C) between the two rooms. Table 3 indicates that
the dial setting should be lowered 5° F (3° C) to compensate
for the 35° F (20° C) temperature difference.
Manual Reset
If the device includes manual reset (L4006E, L4008E),
be sure to press the (red) reset button on the front of
the case to make sure that the controller is not locked
out on safety. When checking the system, adjust the limit
setting low enough so the temperature of the controlled
medium reaches the high limit setting. When the limit set-
ting is reached, the Aquastat Controller locks out and the
burner shuts down. When the temperature of the controlled
medium drops to the high limitsetting, less the differential,
push the manual reset button to make the system operative
again. Reset the control to the proper high limit setting.
Fig. 32. Interstage differential adjustment on an L6008G.
Use with L4006A,B; L6008A.
ADJUSTMENTS
M8790B
WALL
L6008A
CASE
REMOTE
SENSING
BULB
CONTROLLED
SPACE
TEMPERATURE
115
o
F (46
o
C)
ROOM
TEMPERATURE
80
o
F (27
o
C)
Fig. 33. L6008A calibration.
M8972
RIGHT
SWITCH
LEFT SWITCH
STAR WHEEL (INTERSTAGE
DIFFERENTIAL ADJUSTMENT)
1
1
SELECT MODELS HAVE FOUR TERMINALS.