Aquastat L4006,7,8;L6006,7,8

 

9 60-2104—01

220

240

100

120

140

160

180

200

MOUNTING 
HOLES (3)

RIGHT SNAP
SWITCH (NO. 1)

LEFT SNAP 
SWITCH
(NO. 2)

NOTCHES FOR 
CAPILLARY 
TUBE (4)

7/8 IN. (22 MM) 
DIAMETER
KNOCKOUT 
BOTH ENDS

27-1/2 IN. 
(70 MM)
SENSOR

10 FT. (3.0 M)
CAPILLARY 
TUBE

M4673B

1

1 SELECT MODELS HAVE SIX TERMINALS.

Fig. 9.Internal view of L4008L or L6008G..

Mount With Bulb Compression Fitting

1. Screw the fitting into the boiler or pipe tapping.

2. Slide the sealing washer onto the bulb.

3. Insert the bulb into the fitting until the bulb 

bottoms.

4. Slide the split sleeve into the fitting. (See Fig. 

10).

5. Place clamps A and B on the assembly so that 

the sleeve is drawn into the fitting when the 
screws are tigtened .

M8815B

CLAMP B

CLAMP A

CLAMP SCREWS (2)

BULB 
COMPRESSION 
FITTING

SEALING 
WASHER

BULB

INSERTION LENGTH
APPROX. 3-3/16 IN. (81 MM)

SPLIT SLEEVE

Fig. 10. Bulb compression fitting. Use with L4006A,B; 

L6008A.

Fig. 11. Capillary compression fitting. Use with L4008. 

Use with L4006A,B; L6008A.

Mount With Capillary Compression Fitting

1. Screw the fitting into the boiler or pipe tapping. 
2. Place the packing nut on the tubing. 
3. Slide the bulb completely through the fitting. 
4. Place the composition disk and four slotted 

brass washers on the tubing in the order shown 
in Fig. 11. Turn the brass washers so the slots 
are 180 degrees apart 

5. Slide the seal assembly into the fitting and 

tighten the packing nut. 

Duct Mounting 

1. Drill a 3/4 in. (19 mm) hole in the duct wall 

large enough to admit the sensing bulb into 
the holder. 

2. Using the holder as a template, mark and drill 

holes for the bulb holder mounting screws. 
(See Fig. 12). 

3. Break the holder to the desired length. (See 

Fig. 13).

NOTE: The holder must be long enough to hold 

the sensing bulb in freely circulating air 
away from the duct wall. Neatly coil the 
excess capillary at the controller case or 
at the bulb holder.

M8970B

Fig. 12. Bulb support. Use with L4006A,B; L6008A.

MOUNTING

3

4

5

NOTE: Make sure that the nub on clamp A 

engages the space between the sleeve 
and the clamp. 6.

6.  Tighten the clamp screws evenly.

COMPOSITION DISK
(SLOTTED)

BOILER PLUG

CAPILLARY TUBING

EXAMPLE OF SLOTTED WASHERS 
ASSEMBLED 
IN PAIRS:

PACKING NUT

M8816B

IMMERSION
BULB

Содержание Aquastat L4006

Страница 1: ...ntrollers Aquastat Installation Guide GENERAL Aquastat Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers storage tanks and other applications where temperature control is required ...

Страница 2: ...e ordering number If you have additional questions need further information or would like to comment on our products or services please write or phone 1 Your local Honeywell Automation and Control Products Sales Office check white pages of your phone directory 2 Honeywell Customer Care 1885 Douglas Drive North Minneapolis Minnesota 55422 4386 In Canada Honeywell Limited Honeywell Limitée 35 Dynami...

Страница 3: ...so this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed SUPER TRADELINE TRADELINE MODELS SUPER TRADELINE controls offer features not available on TRADELINE or standard models and are designed to replace a wide range of Honeywell and competitive controls TRADELINE models are selected and p...

Страница 4: ...le Insulation depth 1 1 2 in or 3 in 38 mm or 76 mm NPT brass spud 3 4 in 19 mm Screw in front of case on dial sui able for Powerpile control Factory set stop at 240 F 116 C L4006C High or low limit 65 F to 200 F 18 C to 93 C 3 1 2 F 2 C fixed Horizontal direct immersion Breaks TRADELINE model available Less cover Capillary 10 in 254 mm NPT brass spud 3 4 in 19 mm L4006Eb High limit 130 F to 290 F...

Страница 5: ...irect immersion Breaks Remote capillary 5 1 2 ft 1 7 m 8 1 2 ft 2 6 m or 10 ft 3 0 m Factory set scale stops at 120 170 or 200 F 49 77 or 93 C Celsius scale markings Front cover screw L4008B Circulator 100 F to 240 F 38 C to 116 C 5 F 3 C fixed or 5 F to 30 F 3 C to 17 C adjustable Remote bulb direct immersion Makes Capillary 5 1 2 ft 1 7 m L4008Eb High limit 40 F to 80 F 4 C to 27 C or 130 F to 2...

Страница 6: ... 18 C to 93 C 5 F 3 C fixed or 5 F to 30 F 3 C to 17 C adjustable Horizontal or vertical surface mounted TRADELINE model available Strap on surface mount L6007A Circulator and low limit or high limit 40 F to 180 F 4 C to 82 C Fixed Horizontal or vertical Insulation depth 1 1 2 in or 3 in 38 mm or 76 mm L6008A Circulator and low limit cooling 100 F to 240 F 38 C to 116 C or 30 F to 70 F 35 C to 21 ...

Страница 7: ...ect insertion models Fig 2 Approximate installation dimensions in inches mm for remote bulb models Otherdimensions are the same as Fig 1 M8957A KNOCKOUT FOR 3 4 19 CONDUIT ON ALL MODELS SIMILAR KNOCKOUT ON BOTTOM FOR HORIZONTAL INSERTION AND REMOTE BULB MODELS 1 25 5 16 8 2 51 2 1 8 54 5 5 8 136 1 7 8 48 3 16 5 RESET BUTTON L4006E L4008E ONLY KNOCKOUT FOR 3 4 19 CONDUIT ON VERTICAL INSERTION MODEL...

Страница 8: ...deline models as follows Fold the plastic bag of compound lengthwise and twist gently Snip the end of the bag and insert into the well Slowly pull out the bag while squeezing firmly to distribute compound evenly in the well Insert the bulb into the well Bend the tubing if necessary to provide force to hold the bulb against the bottom of the well and to hold the outer end of the bulb firmly in cont...

Страница 9: ...m the boiler tapping 3 Install the immersion well included with the controller If the boiler tapping is greater than 1 2 in 13 mm use a reduction fitting to adapt the boiler opening to the 1 2 in 13 mm threads that are standard with the well or fitting Fittings with 3 4 in 19 mm threads are also available 4 Fill the system Make sure that the well is screwed intightly enough to prevent leakage Do n...

Страница 10: ...er itself or in the feed riser about 6 in 153 mm above the boiler If the riser is valved the bulb can be installed between the boiler and the valve NOTE Do not make sharp bends or kinks in the capillary Make bends no sharper than 1 in 25 mm radius After installing the controller carefully coil the excess capillary at the bottom of the controller case 1 M8777B WELL BULB SPUD MOUNTING CLAMP A DRAW N...

Страница 11: ...Capillary Compression Fitting 1 Screw the fitting into the boiler or pipe tapping 2 Place the packing nut on the tubing 3 Slide the bulb completely through the fitting 4 Place the composition disk and four slotted brass washers on the tubing in the order shown in Fig 11 Turn the brass washers so the slots are 180 degrees apart 5 Slide the seal assembly into the fitting and tighten the packing nut ...

Страница 12: ...r other debris cannot obstruct circulation of air around it and where children cannot reach it Avoid vents from the building Install the case at the indoor location selected fastening the screws through holes in the back of the case Bring out the bulb and tubing through a 3 4 in 19 mm hole in the outside wall avoiding sharp bends or kinks Leave excess tubing coiled near the case Do not make sharp ...

Страница 13: ...f the horizontal suction line between the coil and trap not on the trap 4 Attach the sensing bulb to the suction line with clips or straps See Fig 17 5 Coil the excess length of capillary tubing near the L6008A case 5 Coil the excess length of capillary tubing near the L6008A case Fig 16 Securing remote bulb in clip M8805B L6008A CIRCULATOR LOW LIMIT CONTROLLER CAPILLARY REMOTE BULB SUCTION LINE B...

Страница 14: ...OR AND LOW LIMIT CONTROLLER R W B M8780B COOLING EQUIPMENT INDICATING LIGHT Fig 21 L6008A used to control cooling equipment and indicating light Use with L4006A B L6008A Wiring Disconnect power supply before beginning installation to pre vent electrical shock or equipment damage All wiring must comply with local codes and ordinances regarding wire size type of insulation enclosure etc Figures 19 t...

Страница 15: ...nnection diagram for an oil fired hydronic heating system that provides year round domestic hot water using RA817A Fig 23 Typical oil fired hydronic heating system that provides year round domestic hot water using RA832A Use with L4006A B L6008A L1 HOT L2 1 1 2 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED WHEN USING CIRCULATOR LOW LIMIT CONTROL REMOVE L1 L2 JUMPER 2 L6...

Страница 16: ...BREAKS R W MAKES R B ON FALL BREAKS R W MAKES R B ON FALL INTERSTAGE DIFFERENTIAL DIFFERENCE BETWEEN THE TEMPERATURES AT WHICH THE TWO SWITCHES MAKE R W ADJUSTABLE FROM 3 F TO 10 F 1 7 C TO 5 6 C ON STANDARD MODELS OR FROM 3 6 F TO 12 F 2 0 C TO 6 7 C 55 F TO 175 F 13 C TO 79 C MODELS TWO SPDT SWITCHES OPERATE IN SEQUENCE EACH SWITCH DIFFERENTIAL IS FIXED AT APPROXIMATELY 3 F 1 7 C ON STANDARD MOD...

Страница 17: ... the wheel on the back of the snap switch See Fig 32 until the desired reading is aligned with the V notch in the frame The wheel provides an adjustment from 5 F to 30 F 3 C to 17 C Replace the cover on the Aquastat Controller 1 ADJUSTMENTS Adjust the control point to correspond with the boiler manufacturer recommendations To adjust insert a screwdriver in the slotted screw type head located benea...

Страница 18: ...8A case is located in a room with a lower temperature than the controlled space Adjusting the controlled space setting dial setting is necessary to compensate for the temperature difference of 35 F 20 C between the two rooms Table 3 indicates that the dial setting should be lowered 5 F 3 C to compensate for the 35 F 20 C temperature difference Manual Reset If the device includes manual reset L4006...

Страница 19: ...r Obtain medical atten tion if irritation develops and persists Ingestion Contact physician or local poison control center immediately Inhalation Remove patient to fresh Manufacturer Honeywell Inc 1985 Douglas Drive North Minneapolis MN 55422 Date Released October 8 1999 NFPA Ratings Health 0 Flammability 1 Reactivity 0 Personal Protection B Section 2 Composition Information on Ingredients Section...

Страница 20: ...e gloves and clothing are recommended as material is dif ficult to remove from skin and clothing Other Protective Equipment None required Section 9 Physical and Chemical Properties Appearance Odor Aluminum color semi solid material pleasant odor Solubility in Water Negligible Specific Gravity 0 86 Section 10 Stability and Reactivity Stability Stable Reactivity Hazardous polymerization will not occ...

Отзывы: