Section 3: Programming the GSMHS
3-5
PROMPTS
ENTRY
OPTIONS
DESCRIPTION
13
En. 2
nd
CS Y/N
(N)_
[Y], [N]
Applicable only if control supports Central Station #1
and #2 Category Enable reporting for the LRR device
(e.g., VISTA-128BP, FA1660C, etc.).
Used if reporting to a second central station is desired.
If [N], go to Prompt 17: "Device Address."
14
2
nd
City ID
(??)_
[01-99]
Enter the 2-digit secondary city ID, 01-99 (decimal).
15
2
nd
CS ID
(??)_
[01-FE]
Enter the 2-digit second central station's ID number,
01-FE (HEX).
16
2
nd
Sub ID
(????)_
[0001-9999]
Enter the 4-digit subscriber account number for the
second central station, 0001-9999.
17
Device Address
(03)_
[01-30]
In ECP mode, the GSMHS communicates with the
control panel as a Long Range Radio (LRR) device.
Enter the appropriate ECP device address. For VISTA-
10 and VISTA-20 series control panels, use address 03.
For other controls, see the control panel’s Installation
and Setup Guide.
NOTES:
1. When programming the control panel, enable the
LRR output.
2. The device address must be unique from the "Keypad
Address" entered in Prompt 19.
18
Direct Wire Y/N
(N)_
[Y], [N]
Applies only to VISTA-128BP/250BP and FBP Series
controls.
If [N], skip to Prompt 20: "Supervision."
19
Keypad Address
(28)_
[01-30]
Must be
programmed
if using Direct Wire
downloading.
NOTES:
1. This address must be programmed as an alpha
keypad in the control panel (Device Programming
Mode).
2. This address must be unique from the "Device
Address" entered in Prompt 17.
20
Supervision
(US Hi Line
Sec S)_
US Hi Line
Sec S
The AlarmNet network must hear at least one message
from the device during the supervision interval;
otherwise, AlarmNet notifies the central station that a
communication failure has occurred. This interval
satisfies the 200 second single path comm. fail
requirement.
This interval cannot be changed.
21
Old Alarm Time
10 Minutes_
10 Minutes
15 Minutes
30 Minutes
1 Hour
2 Hours
4 Hours
8 Hours
12 Hours
24 Hours
The old alarm time sets how long an undeliverable
alarm is retried for delivery to the central station. If
the message is not validated, it is retried until the old
alarm time is reached or the message is validated.
Press the [space] key to scroll through choices.
22
GSM Flt Time
(1 min)_
[01-99]
[00] = not used
In the event the module detects a communication path
failure, enter the time delay (in minutes) before the
module notifies the control panel with a trouble
message (and trips the Fault Output if used; (terminal
11) see next prompt). The control panel can then notify
the central station.
UL:
Must be one (01) minute.
Содержание AlarmNet GSMHS
Страница 2: ......
Страница 8: ...GSMHS Installation and Setup Guide 1 4 ...
Страница 32: ...GSMHS Installation and Setup Guide 3 18 ...
Страница 36: ...GSMHS Installation and Setup Guide 4 4 ...
Страница 46: ...GSMHS Installation and Setup Guide B 2 ...
Страница 48: ...GSMHS Installation and Setup Guide C 2 ...
Страница 50: ...GSMHS Installation and Setup Guide D 2 ...
Страница 51: ...NOTES ...
Страница 52: ...NOTES ...
Страница 53: ...NOTES ...