![Honeywell AlarmNet GSMHS Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/honeywell/alarmnet-gsmhs/alarmnet-gsmhs_installation-and-setup-manual_148761011.webp)
Section 2: Mounting and Wiring
2-3
The Telco line fault monitor should utilize either zone 6 or zone 7 on the GSMHS. When
programming the GSMHS ensure the following programming is accomplished. The example
below is for Zone 6.
Programming Prompt
Setting
Enable Zn6
[Y]
Zn6 Trigger Type
[V+]
Invert Zn6
[Y]
Restore Zn6
[Y]
Delay Zn6
[00]
Rpt Zn6 ONLY if Armed
[N]
For ECP and 4204 modes, the line fault monitor should be connected to a control panel zone.
Wiring for ECP, 4204 and Two-4204 Modes
Most Honeywell ADEMCO control panels support LRR-ECP data communication, (e.g.,
VISTA-10P, VISTA-15P, VISTA-20P, VISTA-128BP and VISTA-128FBP). However, there
are some panels that do not. Check the Installation and Setup Guide for the control panel
you are using to see if it supports ECP communication.
Connect the GSMHS to a compatible Honeywell VISTA control panel's ECP terminals, in
parallel with keypads and other peripheral devices such as RF receiver, VIP module, etc.
Wire length/gauge limitations are the same for the module as they are for keypads and other
peripheral devices. To wire the module for ECP or 4204 modes, see
Figure 2-2
and make the
following connections:
COMMUNICATIONS
MODULE
VISTA CONTROL PANEL
iGSMBR-005-V0
GND
GND
ECP DATA IN
2
1
4
5
TB1
TRANSFORMER
AC INPUT 2
AC INPUT 1
J1
BATTERY
+12V AUX
ECP (+) VOLTAGE INPUT
3
DATA IN
ECP DATA OUT
6
DATA OUT
BLK
YEL
RED
GRN
Figure 2-2. Wiring a VISTA for ECP Mode or 4204 Modes
Wiring for Zone Trigger Mode
To trip a zone on the GSMHS in V+ trigger mode, the positive triggering voltage from the
control panel must be within 6V-12V. UL Installations: Use inverted mode.
Trigger levels above this range may cause permanent damage to the unit.
Trigger levels below this range result in unreliable operation.
To trip a zone on the GSMHS in V- trigger mode, the negative triggering voltage must be less
than 1.0V.
Connect a wire from the triggering source (bell output, voltage trigger, etc.) of the control
panel to the zone input of the module, and connect a common ground between the module
and control panel. NOTE: This mode has not been evaluated by UL.
Examples of zone connections follow:
Содержание AlarmNet GSMHS
Страница 2: ......
Страница 8: ...GSMHS Installation and Setup Guide 1 4 ...
Страница 32: ...GSMHS Installation and Setup Guide 3 18 ...
Страница 36: ...GSMHS Installation and Setup Guide 4 4 ...
Страница 46: ...GSMHS Installation and Setup Guide B 2 ...
Страница 48: ...GSMHS Installation and Setup Guide C 2 ...
Страница 50: ...GSMHS Installation and Setup Guide D 2 ...
Страница 51: ...NOTES ...
Страница 52: ...NOTES ...
Страница 53: ...NOTES ...