Section 3: Programming the 7845GSM
3-5
PROMPTS ENTRY
OPTIONS
DESCRIPTION
18
Enable DW Y/N
(N)_
[Y], [N]
Applies only to VISTA-128BP/250BP and FBP Series
controls.
Enables Direct Wire Downloading over GSM.
If [N], skip to Prompt 20: "Supervision."
19
Direct Wire Addr
(28)_
[01-30]
When using Direct Wire downloading, the 7845GSM
communicates with the panel as an alpha keypad to
initiate the direct wire download session. Enter the
appropriate device address.
NOTES:
1. This address must also be programmed as an
alpha keypad in the control panel (Device
Programming Mode). DO NOT connect an actual
keypad (or any other device) assigned to this
address.
2. This address must be unique from the "Device
Address" entered in Prompt 17.
20
Supervision
(24 Hours)_
•
30 Day
•
24 Hour
•
None
The AlarmNet network must hear at least one
supervisory message from the module during this
supervision period; otherwise, AlarmNet notifies the
central station that a communication failure has
occurred. (If the supervision period is changed after
registration, you must re-register the module.)
Press the [space] key to scroll through choices.
21
Old Alarm Time
(10 Minutes)_
•
10 Minutes
•
15 Minutes
•
30 Minutes
•
1 Hour
•
2 Hours
•
4 Hours
•
8 Hours
•
12 Hours
•
24 Hours
The old alarm time sets how long an undeliverable
alarm is retried for delivery to the central station. If
the message is not validated, it is retried until the old
alarm time is reached or the message is validated.
Press the [space] key to scroll through choices.
22
GSM Flt Time
(60 mins)_
[01-99]
[00] = not used
In the event the module detects a communication path
failure, enter the time delay (in minutes) before the
module notifies the control panel with a trouble
message (and trips the Fault Output if used; (terminal
11) see next prompt). The control panel can then notify
the central station.
UL NOTE:
Must be two (02) minutes.
23
Flt Rel ON Y/N
(N)_
[Y], [N]
If enabled, the fault open collector output is normally
energized to ground, and de-energizes (open circuit) in
the event of a module fault. For conditions that trip the
fault relay refer to
Module Supervision Features
in
Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring for
Module Fault Relay
in Section 2.
UL NOTE:
Must be set to "Y."
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A restore
report is sent within 1-3 hours after power is restored.
24
Pwr Loss Rpt Y/N
(Y)_
[Y], [N]
UL NOTE:
Must be set to "Y."