Installation Instructions
4-6
*64
Test Report Code
0 = disable; 1-F = see description above
∗
59
Sent periodically to test that the communicator and phone lines are
operational. Frequency of report is set in Scheduling mode (event 11).
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*65
Open Report Code
0 = disable; 1-F = see description above
∗
59
Sent upon disarming of the system in the selected partitions.
UL: Required for UL commercial burglar alarm installations.
*66
Arm Away/Stay Report Code
0 = disable; 1-F = see description above
∗
59
This option allows for independent programming of Away and Stay
reports for each partition.
NOTE:
“OPEN” reports are not sent if the associated closing report is
not enabled.
*67
RF Low Battery Report Code
0 = disable; 1-F = see description above
∗
59
Sent when a wireless transmitter low-battery condition exists.
UL installations: must be enabled if wireless devices are used.
*68
Cancel Report Code
0 = disable; 1-F = see description above
∗
59
Sent upon disarming of the system after an alarm condition was
reported.
*69
Alarm Restores
Send restore code (if fault cleared):
0 = at siren timeout (if restored) or at disarm
(whether restored or not)
1 = dynamically as the fault clears
2 = only after a disarm
Alarm restore message will be sent upon condition selected.
*70
Alarm Restore Report Code
0 = disable; 1-F = see description above
∗
59
Sent when an alarm zone is restored to its non-faulted condition or at
the times selected in field *69.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*71
Trouble Restore Report Code
0 = disable; 1-F = see description above
∗
59
Sent when a trouble in a zone is restored
UL: Required for commercial burglar alarm installations.
*72
Bypass Restore Report Code
0 = disable; 1-F = see description above
∗
59
Sent when a zone that has been bypassed is unbypassed, either
manually or when the partition/system is disarmed.
UL: Required for commercial burglar alarm installations.
*73
AC Mains Restore Report Code
0 = disable; 1-F = see description above
∗
59
Sent when AC mains has been restored after an AC mains outage.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*74
Low Battery Restore Report Code
0 = disable; 1-F = see description above
∗
59
Sent when a system low-battery condition is restored to normal.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
*75
RF Low Battery Restore Code
0 = disable; 1-F = see description above
∗
59
Sent when a transmitter’s low battery condition is restored (i.e., new
battery installed).
UL installations: must be enabled if wireless devices are used.
Required for UL commercial burglar alarm installations and required
for residential fire alarm installations.
*76
Test Restore Report Code
0 = disable; 1-F = see description above
∗
59
Sent when the Test mode is exited.
UL: Required for UL commercial burglar alarm installations and
required for residential fire alarm installations.
Miscellaneous System Fields
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*77
Summer Time
Start/End Month
0 = Disabled
4 = April
1 = Jan
# + 10 = Oct
2 = Feb
# + 11 = Nov
3 = Mar
# + 12 = Dec
Enter the start and end month for summer time, if applicable to the
region.
*78
Summer Time
Start/End Weekend
0 = disabled
4 = fourth
1 = first
5 = last
2 = second
6 = next to last
3 = third
7 = third to last
Enter the start and end weekend for summer time, if applicable to the
region.