VISTA-40 Installation and Setup Guide
3-24
Power Limiting Outputs
All outputs are power-limited as per UL985/UL1023.
The following table shows the maximum current that
may be drawn from each output.
Output
Maximum Current Draw
Auxiliary Power
750mA
Polling Loop
64mA
Alarm Output
1.7A
For Household Fire or Combination Household
Fire/Burglary Installation:
The total current drawn
from the auxiliary power, the polling loop, and the
alarm output combined must not exceed 750mA to
comply with the battery independence requirements in
UL985.
For Household Burglary-Only Installations:
The
total current drawn from the alarm output may be up to
1.7A. A battery must be installed to supply the current
of the combined auxiliary power, polling loop, and
alarm output in excess of 750mA.
Failure to observe the polling loop current
rating will cause polling loop malfunction.
Failure to observe the auxiliary power current
rating will result in a battery that does not
charge properly or possibly a tripped circuit
breaker.
To connect the transformer to the control, perform the
following steps:
Step Action
1
Connect all installed devices to the control.
2
Wire the 1361 Transformer (1361CN in
Canada) to the panel (before connecting the
battery) as shown in
Figure 3-29
, or wire the
1361X10 Transformer as shown in
Figure 3-
30
(if using X-10 devices).
3
Plug the transformer into a 24-hour,
uninterrupted, 120VAC, 60Hz outlet. After
a few seconds, the keypad display appears.
NO CONNECTION
TRANSFORMER
16.5VAC, 40VA
ADEMCO No.1361
or 1361X10, if X-10
DEVICES WILL BE USED.
Connect to
24hr. source
of AC mains
1
2
3
RED (+)
BLK (-)
Connect to
12VDC, 4AH
or 12VDC, 7AH
GEL CELL
BATTERY
CHARGING
VOLTAGE
13.7VDC
NOTE:
WHEN POWERING UP
THE PANEL, PLUG THE
TRANSFORMER IN BEFORE
CONNECTING THE BATTERY.
BATTERY
TABS
PRIMARY POWER
Supplied by a transformer
which is rated at
16.5VAC, 40VA.
Caution must be taken when
wiring this transformer to the
panel to guard against blowing
the fuse inside the transformer
(non-replaceable).
pwr_bat_conn-001-V1
Figure 3-29: 1361 Transformer and Battery Connections
1
2
3
4
5
6
7
8
9
BLA
CK
BLUE
BR
O
W
N
GREEN
RED
WHITE
YELLOW
GRA
Y
VIOLET
4142TR CABLE
X10 TRANSFORMER/INTERFACE
TERMINALS
ON CONTROL
BOARD
1361X10-001-V0
AC
AC
Sync
Output
Signal
Common
X10
Data
J8 CONNECTOR
Figure 3-30: 1361X10 Transformer Connections
Содержание ADEMCO VISTA-40
Страница 1: ...N7001V5 5 04 Rev A 0 0 2 2 9 9 6 67 7 3DUWLWLRQHG 6HFXULW 6 VWHP QVWDOODWLRQ DQG 6HWXS XLGH ...
Страница 2: ...ii ...
Страница 10: ...VISTA 40 Installation and Setup Guide 2 2 ...
Страница 38: ...VISTA 40 Installation and Setup Guide 3 28 ...
Страница 46: ...VISTA 40 Installation and Setup Guide 4 8 ...
Страница 62: ...VISTA 40 Installation and Setup Guide 6 4 ...
Страница 64: ...VISTA 40 Installation and Setup Guide 7 2 ...
Страница 78: ...VISTA 40 Installation and Setup Guide B 2 ...
Страница 80: ...VISTA 40 Installation and Setup Guide C 2 ...
Страница 82: ...VISTA 40 Installation and Setup Guide D 2 ...
Страница 89: ...NOTES ...
Страница 90: ...NOTES ...
Страница 91: ...NOTES ...
Страница 92: ...NOTES ...
Страница 93: ...NOTES ...
Страница 94: ...NOTES ...
Страница 95: ...NOTES ...