VISTA-40 Installation and Setup Guide
5-2
FIELD
TITLE and DATA ENTRIES
EXPLANATION
*12
Exit Delay #2 (partition-specific)
Enter
03-15
multiplied by 15 seconds.
00
= no delay.
Exit Delay #2 is used for a secondary door requiring a longer delay than
those assigned to Exit Delay #1.
NOTE:
The delay may not exceed 60 seconds for UL installations.
*13
Alarm Sounder Duration
(partition-specific)
Enter
01-15
multiplied by 2 minutes.
00
= no timeout.
Defines the length of time the Bell Output and the keypad’s sounder will
sound for all audible alarms.
Must be minimum 16 minutes for UL Commercial Burglary installations.
*14
Zone 9 Fast/Slow Response
0
= slow 350ms
1
= fast 10ms
Select the response time for devices connected to zone 9.
*15
Keyswitch Assignment
Enter
1-2
partition keyswitch is being used.
Enter
0
if the keyswitch is not used.
The keyswitch requires the use of zone 7 wired loop (zone 7 is no longer
available as protection zone). The fire and panic alarm voltage triggers
(J7) automatically become ARMING and READY status outputs for the
Keyswitch LEDs.
Openings/closing report as user “0” if enabled in field *40.
*16
Confirmation of Arming Ding
(partition-specific)
0
= disable
1
= enable
If enabled, produces ½-second external alarm sounding (“ding”) at the end
of exit delay (or after kissoff from the central station, if sending closing
reports).
Must be 1 for UL installations.
*17
AC Loss Keypad Sounding
0
= disable
1
= enable
If enabled, sounding at the keypad (rapid beeping) occurs when AC power
is lost (sounding occurs about 2 minutes after actual AC loss).
*19
Randomize AC Loss Report
0
= disable
1
= enable
If enabled, randomizes AC loss reporting between 10 and 40 min. after an
actual AC loss.
If disabled, AC loss reporting about 2 minutes after actual AC loss.
Selecting this option helps prevent an overload of AC loss messages at the
central station during a community blackout.
*20
VIP Module Phone Code
1-9
= first digit of access code
or
#
= second digit of access code (enter #
+11 for “
∗
”, or # +12 for “#”)
To disable enter
00
for the 1
st
digit
If a 4285/4286 Voice Module is being used, enter the 2-digit phone code
used to access the system.
Must be disabled for UL installations.
*21
Prevent Fire Timeout
0
= disable (timeout)
1
= enable (no timeout)
If enabled, there is no timeout of the alarm sounder duration for all fire
zones, regardless of partition, so that fire sounding continues until the
system is reset.
If disabled, (timeout) the normal burglary sounder duration (field
✳
13)
applies to fire alarms.
*22
Keypad Panic Enables (partition-
specific)
0
= disable
1
= enable
If enabled, the keypad panics (zones 995, 996, and 999) may be used in
this partition. There are 3 entries in this field, one for each panic.
*23
Multiple Alarms (partition-
specific)
0
= disable
1
= enable
If enabled, allows more than one alarm sounding for a given zone during
an armed period.
NOTE:
that multiple alarm soundings will not occur more frequently
than allowed by the programmed alarm sounder duration. This has no
impact on the number of communication messages transmitted.
Must be 1 for UL installations.
Содержание ADEMCO VISTA-40
Страница 1: ...N7001V5 5 04 Rev A 0 0 2 2 9 9 6 67 7 3DUWLWLRQHG 6HFXULW 6 VWHP QVWDOODWLRQ DQG 6HWXS XLGH ...
Страница 2: ...ii ...
Страница 10: ...VISTA 40 Installation and Setup Guide 2 2 ...
Страница 38: ...VISTA 40 Installation and Setup Guide 3 28 ...
Страница 46: ...VISTA 40 Installation and Setup Guide 4 8 ...
Страница 62: ...VISTA 40 Installation and Setup Guide 6 4 ...
Страница 64: ...VISTA 40 Installation and Setup Guide 7 2 ...
Страница 78: ...VISTA 40 Installation and Setup Guide B 2 ...
Страница 80: ...VISTA 40 Installation and Setup Guide C 2 ...
Страница 82: ...VISTA 40 Installation and Setup Guide D 2 ...
Страница 89: ...NOTES ...
Страница 90: ...NOTES ...
Страница 91: ...NOTES ...
Страница 92: ...NOTES ...
Страница 93: ...NOTES ...
Страница 94: ...NOTES ...
Страница 95: ...NOTES ...