FIELD
TITLE and EXPLANATION
*96
Command to Initialize CSID and Subscriber Account Number
This is a command function, not a data field. Use this command, if necessary, to reset all subscriber account
numbers and the internal CSID to the factory default values.
*97
Command to Reset System to Factory Default Values
This is a command function, not a data field.
Pressing
∗
97 resets all data fields to the factory default values
(shown on the Program Form).
IMPORTANT:
Do not press
∗
97 to load defaults if any programming has been done previously—data
already programmed into the system will be changed!
*98
Command to Exit Program Mode (with installer code lockout)
Exits Programming Mode and prevents re-entry by:
Installer Code + [8] + [0] + [0]. To enter the programming mode if
∗
98 was used to exit, you must first
power the system down. Then power up again, and press [
∗
] and [#] at the same time, within 50 seconds
of powering up.
See field *88 for other Program mode lockout options.
*99
Command to Exit Program Mode
Exits Programming Mode and allows re-entry by:
Installer Code + [ 8] + [0] + [0] or by: Pressing [
∗
] and [#] at the same time, within 50 seconds of power-up.
Pager Programming Fields
FIELD
TITLE and EXPLANATION
*160
Pager 1 Phone No.
Enter the pager phone number. If you enter fewer than 20 digits, exit by pressing [
∗
] and next field
number. To clear entries from this field, press
∗
160
∗
.
*161
Pager 1 Characters
Enter up to 16 optional characters, which may be sent as a prefix to the 7-digit system status code sent
to Pager 1 (if used). Phone number in field *160 must be entered. If fewer than 16 characters, exit by
pressing [
∗
] and next field number. To clear entries from this field, press
∗
161
∗
.
For example, these optional 16 characters may be composed of the following:
•
paging company PIN number, subscriber account number,
∗
(enter # + 11 to send
∗
), # (enter # + 12
to send #), pause (enter # + 13 to allow a 2-second pause; some paging systems require pause)
•
Any special character(s) the end user may decide to transmit
The format for the 7-digit system status code is defined as follows:
Pager Format: XXX-YYYY where:
XXX
= 3-digit event code: 911 = Alarm
101 = Opening (disarm)
811 = Trouble
102 = Closing (arm AWAY)
YYYY = 4-digit user or zone number (depending on type of event).
The first digit is “1,” followed by the 3-digit user or zone number, or “0,” followed by a 3-digit
device address number.
Example 1.
Pager displays:
9 1 1 – 1 0 0 4 :
an alarm (911) caused by a fault in zone 4 (1004).
Example 2.
Pager displays:
1 0 2 – 1 0 0 5 :
a closing–system arming (102) by User 5 (1005).
*162
Pager 1 Report Options
Enter the types of reports to be sent to the pager.
Open/close reports go to pager only when arming (close)/disarming (open) from a keypad using a
security code; auto-arming/disarming, arming with assigned button, and keyswitch arming do not send
pager messages.
Miscellaneous System Fields
*172
Pager Delay Option for Alarms
Enter the desired pager delay (none, 1, 2, or 3 minutes) for alarms. This delay applies to all pagers in
the system.
*177
Device Duration 1, 2
Enter the desired duration for output action options 5 (duration 1) and 6 (duration 2) programmed in
∗
80 Output Function Programming.
*181
50/60 Hz AC Operation
Select the type of AC power applied to the control (option is used for Real-Time Clock synchronization).
Installation Instructions
4-8
Содержание ADEMCO VISTA-10P
Страница 36: ...Installation Instructions 4 12 ...
Страница 52: ...Installation Instructions 5 16 ...
Страница 64: ...Installation Instructions 8 4 ...