On-Board Triggers
Connect field wiring to the desired trigger pin on
the 8-pin trigger connector centrally located
above the terminal strip.
You can use a 4-wire cable as shown.
UL
If on-board triggers are used, the wiring between
the control unit and the UL Listed device must be run
in conduit, be no more than 3 feet apart and have no
intervening barriers or walls.
4-WIRE CABLE
00-trigcon-005-V3
+12 A
UX.
GND (-)
OUTPUT 17
OUTPUT 18
(RED)
(YELLO
W)
(BLA
CK)
(GREEN)
1
3
4
5
5-PIN TRIGGER CONNECTOR
KEY
Figure 12.
On-Board Trigger Connector with 4-Wire Cable
NOTES
•
There are two on-board triggers that can be used to activate output devices.
•
These outputs are normally high, and go low upon programmed condition.
•
Outputs can be programmed for inverted operation (normally low, go high) using *79 Menu mode.
•
Program these triggers using *80/*81 Menu modes as you would for any other relay output.
•
When using these outputs, note:
pin 1 = output number 17 (trigger 1):
15 ohms to ground when closed (output low), open when off (output high, normal default); can
be used to reset smoke detector power (must set “output normal low = yes” in *79 Menu mode,
and set for zone type 54, fire zone reset, in *80 Menu mode); or can support 12V relay module†
that draws less than 100mA
pin 5 = output number 18 (trigger 2):
100 ohms to ground when closed (output low); open when off (output high, normal default); or
can support 12V relay module that draws less than 20mA
† e.g., Altronix AX-RBS
Phone Line/Phone Module Connections
1.
Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack)
as shown in the Summary of Connections diagram at the back of this manual. Wire colors
represent the colors of the cable to the RJ31X jack.
If using a phone module, continue with the following steps.
2. Make 12V (+) and (–) and data in and data out connections from the phone module to the control,
using the connector cable supplied with the phone module, then insert the keyed connector at the
other end of the connector cable into the header on the phone module.
3. Connect Phone Module terminals as shown below. Use an RJ31X jack with a direct-connect cord
and make all connections exactly as shown.
4. Caller ID Units: If a Caller ID unit is being used, connect the unit directly to the “Handset”
terminals (21 & 22) on the control, as shown.
NOTES
•
Use 4285 or 4286 Phone Modules.
Compatibility: 4286 Phone Modules must have software version WA4286-15.1 or higher (refer to the
label on the square 4286 microprocessor chip).
•
Only one phone module can be used.
•
The phone lines must be in service for the phone module to function, even when accessing the system
from an on-premises phone.
•
If you are also using an Audio Alarm Verification (AAV) unit, refer to
Audio Alarm Verification
(AAV)
section for special wiring connections.
CAUTION:
To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord for
phone line connections.
Installation Instructions
2-10
Содержание ADEMCO VISTA-10P
Страница 36: ...Installation Instructions 4 12 ...
Страница 52: ...Installation Instructions 5 16 ...
Страница 64: ...Installation Instructions 8 4 ...