FIELD
TITLE and EXPLANATION
*76
Test Restore Report Code
Enter the appropriate report code, which is sent when the Test mode is exited.
UL: Required for UL commercial burglar alarm installations and for residential fire alarm installations.
Miscellaneous System Fields
FIELD
TITLE and EXPLANATION
*77
Daylight Saving Time Start/End Month
Enter the start and end month for daylight savings time, if applicable to the region.
*78
Daylight Saving Time Start/End Weekend
Enter the start and end weekend for daylight savings time, if applicable to the region.
*79
Output Device Mapping Menu Mode
Use this menu mode to enter output devices/powerline carrier devices into the system. See Output Device
Programming section for procedures.
*80
Output Programming Menu Mode
Use this menu mode to define output functions for use with output devices/powerline carrier devices. See
Output Programming section for procedures.
*81
Zone List Programming Menu Mode
Use the menu mode to define zone lists. See Zone List Programming section.
*82
Alpha Descriptor Programming Menu Mode
Use this menu mode to assign alpha descriptors to zones.
*84
Auto-Stay Arm
If enabled, the system will automatically change AWAY mode to STAY mode if the entry/exit door
is not
opened and closed within the exit delay time after a user arms in AWAY mode from a wired keypad (non-
RF device). An Opening report followed by an Armed Stay report is sent to the Central Station.
If the door
is
opened and closed within the exit delay period, the system remains in AWAY mode.
Any RF device that arms the system AWAY overrides this feature and the system remains armed AWAY.
*85
Cross Zone Timer
Select the maximum amount of time in which two cross zones must be tripped in an armed system to
send an alarm message to the Central Station. If only one cross zone is tripped during this time, a
trouble message (CID code 380) for that zone is sent to the Central Station.
Assign cross zone pairs in zone list 4. This option not for use in UL installations.
*86
Cancel Verify Keypad Display
Select whether “
ALARM CANCELED
”
is displayed on the LCD keypad under the following conditions:
•
After the kissoff of the cancel message to the Central Station, indicating a successful transmission.
•
When an alarm is successfully canceled before the Central Station received the Alarm message. E.g., if
an alarm is incorrectly triggered and the user presses code + OFF before the dial delay time has
expired, the message will never go out to the CS.
•
When the Cancel report is not enabled and the system is disarmed:
a.
before
dialer delay expires (alarm report not sent) message “Alarm Canceled” is displayed.
b.
after
dialer delay expires message “Alarm Canceled” is not displayed.
*87
Misc. Fault Delay Time
Enter the desired fault delay time. Used with zones assigned to a configurable zone type with fault delay
on (configurable zone type digit “6”), and sets a zone response time of 15 seconds to 15 min. It can be
assigned to zones with sensors that provide a trouble indication when an oil tank is low, or similar
applications for critical condition monitoring where a non-alarm response is desired.
UL: May only be used on non-burglar alarm and non-fire alarm zones when used on a fire and/or UL
burglar alarm installation.
*88
Program Mode Lockout Options
0 = standard *98 installer code lockout (reentry only by [
∗
] + [#] within 50 secs after power up or
downloader)
1 = lockout [
∗
] + [#] reentry after *98 exit (reentry only by installer code or downloader)
2 = not used
3 = lockout all local programming after *98 exit (reentry by downloader only)
Installation Instructions
4-6
Содержание ADEMCO VISTA-10P
Страница 36: ...Installation Instructions 4 12 ...
Страница 52: ...Installation Instructions 5 16 ...
Страница 64: ...Installation Instructions 8 4 ...