4-50
MAN0448_Issue 13_01-2010
5704 Control System
005704-M-5001 A03249
CHAPTER 4 - INSTAllATION INSTRUCTIONS
15.2 Individually Powered Control Cards
Notes: 1. In individually powered control systems a DC connection is
still required to the DC Input Card in order to provide power
to the Engineering Card.
2. The supply to each control card must be externally fuse rated
at 2A maximum.
Individually powered control cards may be required for two reasons:
a. Where the local or other regulations dictate individual connections
in order to achieve the highest integrity for power distribution.
b. In densely populated racks to reduce the current load on the
backplane.
The System 57 DC Input Card supply is fused at 10A and to ensure
reliable operation of the system, the maximum continuous current flow
in the rack backplane should be less than 8A. In 16 channel racks,
substantially populated with four channel catalytic control cards, this
backplane current can be exceeded, especially where long sensor
cable runs are present. Therefore, as a general rule, where more than
eight catalytic control cards are used in a single rack, these should be
powered using the individually powered scheme.
Individual powering of a four channel control card is easily achieved
as follows:
(1) On the Four Channel Control Card, remove the link LK1 from
position 1 - 2 and refit in position 2 - 3 as shown below:
(2) Wire the +24V DC power supply to the respective Quad Relay
Interface Card terminals 35 (+24V) and 36 (0V) as shown above:
Four Channel Control
Card Catalytic Input
Four Channel Control
Card 4 - 20mA Input
lK1
35
36
+24V
(18V to 32V)
0V
1 2 3
External
Fuse 2A
Maximum
Содержание 5704
Страница 1: ...System 57 5704 Control System Operating Instructions ...
Страница 4: ...4 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 ...
Страница 6: ...6 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 User Notes ...
Страница 14: ...1 8 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 User Notes ...
Страница 41: ...2 27 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 Chapter 2 System Description User Notes ...
Страница 63: ...3 22 Chapter 3 Controls and Facilities MAN0448_Issue 13_2010 5704 Control System 005704 M 5001 A03249 ...
Страница 121: ...4 58 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 Chapter 4 Installation Instructions User Notes ...
Страница 183: ...8 14 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 Chapter 8 Specification User Notes ...
Страница 187: ...9 4 Chapter 9 Ordering Information MAN0448_Issue 12_01 2010 5704 Control System 005704 M 5001 A03249 ...