8-6
MAN0448_Issue 13_01-2010
5704 Control System
005704-M-5001 A03249
CHAPTER 8 - SPECIFICATION
Display/Alarm Point:
Linearity:
±2% fsd.
Repeatability:
±2% fsd.
Remote Facilities:
Inhibit/Alarm Reset.
Remote Inhibit / Reset Inputs
Active For Inputs:
More than 2V.
Maximum Input Voltage:
32V.
Maximum Input Current:
5mA.
DC Supply:
18V to 32V dc.
Electronic Drift:
Less than ±3% / 6 months.
Dimensions:
Height:
132mm.
Width:
25mm.
Depth:
172mm.
Weight:
170g.
5.4 Four Channel Control Card - Catalytic
Power Consumption:
12.8W (maximum at 200mA sensor
current).
8.5W (typical).
Drive:
Constant Current.
Initial Accuracy:
±1%.
Current Adjustment:
E
lectronic in 1mA stepsfrom 90 to
315mA.
Maximum Drive Voltage:
10V.
Protection:
Protected against short circuit and
open circuit.
Maximum Line Resistance:
40 ohms (including sensor) at
200mA.
Full Scale Signal Range:
15mV to 300mV.
Bridge Imbalance Default Limits: ±100mV from centre at 2V bridge
voltage.
Adjustment:
Electronic adjustment of bridge
balance and signal gain.
Содержание 5704
Страница 1: ...System 57 5704 Control System Operating Instructions ...
Страница 4: ...4 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 ...
Страница 6: ...6 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 User Notes ...
Страница 14: ...1 8 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 User Notes ...
Страница 41: ...2 27 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 Chapter 2 System Description User Notes ...
Страница 63: ...3 22 Chapter 3 Controls and Facilities MAN0448_Issue 13_2010 5704 Control System 005704 M 5001 A03249 ...
Страница 121: ...4 58 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 Chapter 4 Installation Instructions User Notes ...
Страница 183: ...8 14 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 Chapter 8 Specification User Notes ...
Страница 187: ...9 4 Chapter 9 Ordering Information MAN0448_Issue 12_01 2010 5704 Control System 005704 M 5001 A03249 ...