4-41
CHAPTER 4 - INSTAllATION INSTRUCTIONS
MAN0448_Issue 13_01-2010
5704 Control System
005704-M-5001 A03249
13. OUTPUT CONNECTIONS
13.1 Relay Outputs
Note: The
FAULT
relay is permanently configured for normally
energised
operation in the non-fault condition.
CAUTION
When mains ac is connected to the relay contacts:
a. The ac supply should be fused at 5A maximum.
b. A safety earth connection should be made to the ground
terminal of the relay card.
There are two relay card types providing different levels of alarm relay
capability (See Chapter 2 Section 5).
The cabling to the relays should where possible be kept away from the
sensor cabling, especially those cables carrying mains supplies. The
following figure shows the relay contact connections as shown on the
terminal block.
Com
NO
NC
Energised
Contact
Position
Com
NO
NC
De-energised
Contact
Position
De-energised and Energised Relays Showing Contact Positions
The alarm relays may be configured for either normally de-energised or
normally energised operation. Check the configuration sheet supplied
with the system to determine the operating mode of the relays on each
channel. The energisation mode of the relays can be reconfigured easily
using a computer attached to the Engineering Port. Contact Honeywell
Analytics or your local agent for more information.
Содержание 5704
Страница 1: ...System 57 5704 Control System Operating Instructions ...
Страница 4: ...4 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 ...
Страница 6: ...6 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 User Notes ...
Страница 14: ...1 8 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 User Notes ...
Страница 41: ...2 27 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 Chapter 2 System Description User Notes ...
Страница 63: ...3 22 Chapter 3 Controls and Facilities MAN0448_Issue 13_2010 5704 Control System 005704 M 5001 A03249 ...
Страница 121: ...4 58 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 Chapter 4 Installation Instructions User Notes ...
Страница 183: ...8 14 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 Chapter 8 Specification User Notes ...
Страница 187: ...9 4 Chapter 9 Ordering Information MAN0448_Issue 12_01 2010 5704 Control System 005704 M 5001 A03249 ...