2. Specifications
2.1. Performance Specifications
24
2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide
R200
Honeywell
May 2010
Preset/auxiliary function Input Specifications
Table 3 – Preset/auxiliary function Input Specifications
Item
Specification
Input voltage
24V DC
(15.2V–26.4V)
12V DC
(10.8V–13.2V)
5V DC
(4.1V–5.5V)
Input current
3–6 mA
3–6 mA
3–6 mA
ON guaranteed voltage
15.2 V
10.8V
4.1V
OFF guaranteed voltage
3.2V
2.5V
1.4V
ON delayed time
Less than or equal to 1ms
OFF delayed time
Less than or equal to 1ms
Transistor Output (SINK) Specifications
Table 4 – Transistor Output (SINK) Specifications
Item
Specifications
Rated output
DC 24V, 100mA / point
Leaked current
Less than or equal to 0.1mA
Saturated area voltage
Less than or equal to 1.3V
ON delayed time
Less than or equal to 0.1ms
OFF delayed time
Less than or equal to 0.1ms
Содержание 2MLF-HD2A
Страница 18: ...Contents Figures xviii 2MLF HO2A 2MLF HD2A High Speed Counter Module User s Guide R200 Honeywell May 2010 ...
Страница 121: ...7 Programming 7 4 Basic Program R200 2MLF HO2A 2MLF HD2A High Speed Counter Module User s Guide 121 May 2010 Honeywell ...
Страница 178: ...7 Programming 7 6 Program 178 2MLF HO2A 2MLF HD2A High Speed Counter Module User s Guide R200 Honeywell May 2010 ...
Страница 222: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...